| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A SITE DRAWING SHOWING THE GENERATOR ROOM |
| | AND THE EXHAUST TERMINATION LOCATION MEETS THE 10 FEET |
| | SETBACK FROM PROPERTY LINES. ALSO PROVIDE A DRAWING |
| | THAT SHOWS WHERE THE EXTERIOR FILL TANK IS TO BE |
| | LOCATED ON THE PROPERTY. FBC 107.3.5 |
| | |
| | 2) PROVIDE A DETAIL DRAWING SHOWING THE LOCATION OF THE |
| | INTAKE LOUVER FOR THE GENERATOR ROOM. THE ORIGINAL |
| | APPROVED SHEET A0-101 INDICATES THE WALL THAT THE |
| | INTAKE LOUVER IS TO BE INSTALLED IS A 2 HOUR RATED |
| | WALL. THIS WALL APPEARS TO BE INSIDE THE FOOTPRINT OF |
| | THE BUILDING. THE INTAKE SHOULD BE OUTSIDE OF THE |
| | BUILDING. FMC 401.4 |
| | |
| | 3) SHEET A0-101 OF THE ORIGINAL APPROVED PLANS SHOW THE |
| | GENERATOR ROOM HAVING THE TX VAULT ROOM AND THE |
| | ELECTRIC ROOM SURROUNDING IT. PROVIDE A DETAIL DRAWING |
| | SHOWING THE FUEL PIPING AND TANK VENTILATION LOCATION |
| | ON THE EXTERIOR OF THE BUILDING. FBC 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |