| 2023-03-02 08:44:43 | ELECTRIC REVIEW FAILED |
| | |
| | 1) IT APPEARS THE GENERATOR SUBMITTAL SPECIFICATIONS DO |
| | NO NOT MATCH DRAWING PROVIDE. PLEASE CORRECT AS |
| | APPLICABLE. |
| | |
| | FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL |
| | |
| | 2) PLEASE PROVIDE A CLEAR RISER DETAILING ALL ELECTRIC |
| | LOADS, EQUIPMENT, CONDUIT, AND CONDUCTORS AND |
| | OVERCURRENT PROTECTION. PROVIDE A SYMBOL LEGEND FOR ANY |
| | EQUIPMENT DETAILED WITH ABBREVIATIONS. PLEASE NOTE, |
| | THAT RISER SHOULD NOT CONFLICT WITH PREVIOUSLY APPROVED |
| | RISER DIAGRAMS. INDICATE FIRE PUMP WIRING COMPLIES WITH |
| | ALL RELEVANT NEC CODES, AS PER ARTICLE 695. |
| | |
| | NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE |
| | AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER |
| | DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF |
| | THE FEEDERS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |