Plan Review Notes
Plan Review Notes For Permit 23010854
Permit Number 23010854
Review Stop B
Sequence Number 1
Notes
Date Text
2023-02-24 08:29:46PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE HEIGHT AND SHAPE OF THE BUILDING ARE USED TO
 DETERMINE THE REQUIRED COMPONENT AND CLADDING
 PRESSURES. THE ENGINEER NEEDS TO USE THAT INFORMATION
 TO DETERMINE THE PRESSURES. THE ROOF HEIGHT OF THIS
 BUILDING IS MORE THAN 80 FEET. HAVE THE ENGINEER
 DETERMINE THE PRESSURES AND SUBMIT DIGITALLY SIGNED AND
 SEALED ENGINEERING. FBC 1603.1.4 AND FS 471
  
 2) I DID NOT SEE THAT YOU SELECTED THE MULLIONS THAT
 WILL BE USED. AFTER THE ENGINEER PROVIDES THE REQUIRED
 OPENING PRESSURES. SELECT THE APPROPRIATE ITEMS FROM
 THE PRODUCT APPROVALS AND SPECIFY THEM BY HIGH LIGHTING
 OR CIRCLING THEM. FBC 107.2.1