| Plan Review Notes For Permit 23010834 |
| Permit Number |
23010834 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-20 19:36:46 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC EB 702.5, REVISE PLAN TO SHOW WHAT TYPE OF | | | WINDOW IS BEING REPLACED. IT APPEARS THAT THE PROPOSED | | | WINDOW DOES NOT FALL UNDER THIS EXCEPTION AND ALSO DOES | | | NOT COMPLY WITH EMERGENCY ESCAPE OPENING REQUIREMENTS. | | | | | | 2. FBC EB 702.5, PROVIDE EGRESS WINDOW CLEAR OPENING | | | DIMENSIONS FROM THE MANUFACTURER. | | | | | | | | | | | | |
|