| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL22854-R1 |
| | IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF WEST PALM |
| | BEACH IS NOT LOCATED IN A HVHZ. YOU MIGHT CONSIDER |
| | USING FL7473-R9. |
| | 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL14317-R13 |
| | COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECT |
| | ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.1 |
| | DIRECT-TO-DECK PAGES #4 OR #5. SYSTEM SELECTED MUST |
| | MEET OR EXCEED -70 MAXIMUM DESIGN PRESSURE. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | 3. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL14826-R6 COVERS MULTIPLE DESIGN PRESSURE |
| | RATINGS. PLEASE SELECT CORRECT PLYWOOD SPECIES GROUP, |
| | ANCHOR QUANTITY PAGE #1 OF THE INSTALLATION |
| | INSTRUCTIONS THAT MEET OR EXCEED THE MINIMUM DESIGN |
| | PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE CATEGORY C |
| | AREAS. (-70). ALL APPLICABLE DETAILS AND ATTACHMENTS |
| | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| | DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| | COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| | ENGINEERING. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |