| | BUILDING REVIEW DENIED: |
| | |
| | |
| | 1.) NOTICE: ALL PLAN PAGES NEED TO HAVE A VALID |
| | SIGNATURE/SEAL, SEE BELOW: |
| | |
| | A.) DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND |
| | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A |
| | VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND |
| | SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A |
| | VALID DIGITAL SIGNATURE. |
| | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR |
| | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH |
| | 61G1-16 AND 61G15, F.A.C. |
| | B.) SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE. |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. |
| | 481, F.S. & 61G1. |
| | |
| | 2.) FBC B 107.2.1, PROVIDE DIMENSIONS OF LANDINGS AND |
| | STAIR WIDTH. |
| | |
| | 3.) FBC B 107.2.1, PROVIDE DETAILS OF FINISH DECKING |
| | (EXAMPLE 2"X 6" P.T. OR 5/4" P.T. DECK BOARDS). |
| | |
| | 4.) FBC B 107.2.1, PROVIDE CONNECTION DETAILS FOR 2"X |
| | 6" JOIST TO 2"X 8" SIDE GIRDERS. |
| | |
| | 5.) FBC B 107.2.1 & FBC B 1607.8.1.1, PROVIDE MORE |
| | DETAILS OF HAND RAILS INCLUDING CONNECTIONS. INDICATE |
| | ON PLANS THAT THE HANDRAILS SHALL BE DESIGNED TO RESIST |
| | A CONCENTRATED LOAD OF 200 POUNDS IN ACCORDANCE WITH |
| | ASCE-7. |
| | |