Plan Review Notes
Plan Review Notes For Permit 23010779
Permit Number 23010779
Review Stop P
Sequence Number 2
Notes
Date Text
2023-04-18 08:19:302ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. PAGE G-003, DETAIL #14 -- 2020 FPC 405.3.1 - YOU'VE
 NOTED 29" MIN CLEAR FOR THE URINAL. ALL FIXTURES
 REQUIRE 30 INCHES WIDTH AND 15 FROM CENTER CLEAR SPACE
 FOR THE FIXTURE TO ANY WALL OR PARTITION.
  
 2. DONE
  
 3. DONE
  
 4. P-501 - 2020 FPC 607.1.1 -- ALL HOT WATER MUST GO
 THROUGH A MIXING DEVICE. 1017 MIXING DEVICES ARE ABLE
 TO PRODUCE HOT WATER ABOVE 120 IF NECESSARY. IF YOU
 REQUIRE MORE THAN ONE TEMPERATURE OF HOT WATER OUTPUT,
 THEN MORE THAN ONE MIXING DEVICE CAN BE INSTALLED AND
 SET TO EACH DESIRED TEMPERATURE. BUT, UNDER NO
 CIRCUMSTANCE CAN ANY AMOUNT OF HOT WATER BE DELIVERED
 WITHOUT A MIXING DEVICE.
  
 5. DONE
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  