| Notes |
| Date |
Text |
| 2023-04-18 08:19:30 | 2ND PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. PAGE G-003, DETAIL #14 -- 2020 FPC 405.3.1 - YOU'VE | | | NOTED 29" MIN CLEAR FOR THE URINAL. ALL FIXTURES | | | REQUIRE 30 INCHES WIDTH AND 15 FROM CENTER CLEAR SPACE | | | FOR THE FIXTURE TO ANY WALL OR PARTITION. | | | | | | 2. DONE | | | | | | 3. DONE | | | | | | 4. P-501 - 2020 FPC 607.1.1 -- ALL HOT WATER MUST GO | | | THROUGH A MIXING DEVICE. 1017 MIXING DEVICES ARE ABLE | | | TO PRODUCE HOT WATER ABOVE 120 IF NECESSARY. IF YOU | | | REQUIRE MORE THAN ONE TEMPERATURE OF HOT WATER OUTPUT, | | | THEN MORE THAN ONE MIXING DEVICE CAN BE INSTALLED AND | | | SET TO EACH DESIRED TEMPERATURE. BUT, UNDER NO | | | CIRCUMSTANCE CAN ANY AMOUNT OF HOT WATER BE DELIVERED | | | WITHOUT A MIXING DEVICE. | | | | | | 5. DONE | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | |
|