Plan Review Notes
Plan Review Notes For Permit 23010779
Permit Number 23010779
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-30 11:05:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 23010779 1815 PALM BEACH LAKES BLVD # 05
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL.
 PLAN SHEET G003-ACCESIBILITY GUIDELINES
 ***A) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS.
 ***B) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 ***C) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
  
 2. WASTES THAT DO NOT REQUIRE TREATMENT OR SEPARATION
 SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR OR
 SEPARATOR. THIS INCLUDES BUT IS NOT LIMITED TO DRAINS
 FROM ICE BINS, HAND SINKS. PLEASE REVIEW YOUR DRAINAGE
 PLAN AND MAKE CORRECTIONS AS REQUIRED PER FBC PL
 1003.2, 1003.3.1; PROVIDE PLAN AND RISER DIAGRAM FOR
 SANITARY DRAIN PIPING RECEIVING THE DISCHARGE OF NEW
 ICE BINS, HAND SINKS AND ANY OTHER NEW EQUIPMENT THAT
 IS NOT ALLOWED TO DISCHARGE TO THE INTERCEPTOR. PROVIDE
 POINTS OF CONNECTION TO EXISTING SANITARY.
  
 3. PROVIDE REVISED CALCULATIONS AND STANDARD FOR SIZING
 OF THE GREASE INTERCEPTOR. FBC PL 1003.3.5
  
 4. P111/KEYED NOTE 1: REPLACE EXISTING WATER HEATER
 WITH NEW. REFERS TO WATER HEATER DETAIL ON P501. DETAIL
 DOES NOT EXIST. PLEASE PROVIDE DETAIL OF WATER HEATER
 SHOWING HEATER, PIPING INCLUDING CW, HW, VALVES
 (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE FBC PL
 504.2) , TEMPERATURE ACTUATED MIXING VALVE ASSE 1017
 FOR THE HOT WATER DISTRIBUTION, SIZED THERMAL EXPANSION
 CONTROL DEVICE IF DOWNSTREAM OF CHECK VALVE OR BACKFLOW
 PREVENTER, T&P DISCHARGE INCLUDING TERMINATION AND
 WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION) PER
 WPB FPC 107.2.1, 107.3.5.1.3(5) ; COMPLY WITH FBC PL
 607.1.1, 607.3, 613.1, 503.1, 504.1, 504.4, 504.4.1,
 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2.
  
 5. PROVIDE MATERIAL SPECIFICATIONS FOR WATER, DRAINAGE
 AND VENT PIPING. FBC PL CHAPTER 6,7,9
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
2023-01-25 16:23:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 23010779 1815 PALM BEACH LAKES BLVD # 05
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED
 ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING
 THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED
 PRIOR TO A PLUMBING REVIEW APPROVAL.
 PLAN SHEET G003-ACCESIBILITY GUIDELINES
 ***A) PER FBC ACC 604.8, TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND GRAB BARS.
 ***B) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 ***C) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
  
 2. WASTES THAT DO NOT REQUIRE TREATMENT OR SEPARATION
 SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR OR
 SEPARATOR. THIS INCLUDES BUT IS NOT LIMITED TO DRAINS
 FROM ICE BINS, HAND SINKS. PLEASE REVIEW YOUR DRAINAGE
 PLAN AND MAKE CORRECTIONS AS REQUIRED PER FBC PL
 1003.2, 1003.3.1; PROVIDE PLAN AND RISER DIAGRAM FOR
 SANITARY DRAIN PIPING RECEIVING THE DISCHARGE OF NEW
 ICE BINS, HAND SINKS AND ANY OTHER NEW EQUIPMENT THAT
 IS NOT ALLOWED TO DISCHARGE TO THE INTERCEPTOR. PROVIDE
 POINTS OF CONNECTION TO EXISTING SANITARY.
  
 3. PROVIDE REVISED CALCULATIONS AND STANDARD FOR SIZING
 OF THE GREASE INTERCEPTOR. FBC PL 1003.3.5
  
 4. P111/KEYED NOTE 1: REPLACE EXISTING WATER HEATER
 WITH NEW. REFERS TO WATER HEATER DETAIL ON P501. DETAIL
 DOES NOT EXIST. PLEASE PROVIDE DETAIL OF WATER HEATER
 SHOWING HEATER, PIPING INCLUDING CW, HW, VALVES
 (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE FBC PL
 504.2) , TEMPERATURE ACTUATED MIXING VALVE ASSE 1017
 FOR THE HOT WATER DISTRIBUTION, SIZED THERMAL EXPANSION
 CONTROL DEVICE IF DOWNSTREAM OF CHECK VALVE OR BACKFLOW
 PREVENTER, T&P DISCHARGE INCLUDING TERMINATION AND
 WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION) PER
 WPB FPC 107.2.1, 107.3.5.1.3(5) ; COMPLY WITH FBC PL
 607.1.1, 607.3, 613.1, 503.1, 504.1, 504.4, 504.4.1,
 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2.
  
 5. PROVIDE MATERIAL SPECIFICATIONS FOR WATER, DRAINAGE
 AND VENT PIPING. FBC PL CHAPTER 6,7,9
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  