| 2023-01-31 10:10:09 | FBC- 2020 RES. GAS REVIEW | | | PERMIT- 23010769 | | | 1/31/23 | | | | | | CODES IN EFFECT: | | | FBC B- FLORIDA BUILDING CODE RESIDENTIAL 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) GAS DRAWING: PLEASE INDICATE A NEW OR EXISTING GAS | | | METER ON THE PLAN AND CLARIFY IF IT WILL BE INSTALLED | | | ON THE EXTERIOR WALL OR OUT IN THE YARD- SEC. 107.2.1 | | | WPB. | | | | | | 2) GAS DRAWING: SHOW THE BTU LOAD OF THE GENERATOR- | | | SEC. G2413.3 FBC RES. | | | | | | 3) GAS DRAWING; SHOW THE CLEARANCE DISTANCE FROM THE | | | GENERATOR EXHAUST TO GRAVITY AND MECHANICAL AIR INTAKES | | | TO THE BUILDING- R303.5.1 FBC RES. | | | | | | 4) PROVIDE A GAS RISER DRAWING- SEC. 107.3.5.3 (13) | | | WPB. SHOW THE SIZE OF THE MAIN SUPPLY PIPE, SIZE AND | | | TYPE OF RISER CONNECTING THE METALLIC TO THE PE, | | | LOCATION OF GENERATOR SHUT OFF VALVE AND REGULATOR, AND | | | TYPE AND SIZE OF PIPING CONNECTING TO THE GENERATOR- | | | SECS. G2413.3, G2415.17.1 G2420.1, G2421.1, AND G2422.1 | | | FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|