| Plan Review Notes For Permit 23010640 |
| Permit Number |
23010640 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-07 07:34:37 | 1ST REVIEW FMC | | | PERMIT: 23010640 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THERE APPEARS TO BE MORE THAN ONE STRUCTURE ON THIS | | | PROPERTY. IDENTIFY WHICH STRUCTURE IS TO RECEIVE THIS | | | NEW MECHANICAL SYSTEM. FBC 107.3.5 | | | | | | 2) OUR RECORDS DO NOT SHOW THERE WAS EVER A MECHANICAL | | | SYSTEM PERMITTED FOR THIS ADDRESS. PROVIDE THE ENERGY | | | CALCULATIONS FOR THIS PROJECT. FEC 101.5.1.1 | | | | | | 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | | FOR THIS PROJECT. FRC M1401.3 | | | | | | 4) THE CONDENSER MODEL NUMBERS ON THE DRAWING DO NOT | | | MATCH WHAT IS ON THE SUBMITTED AHRI SHEET. THEY WILL | | | NEED TO MATCH. FBC 107.3.5 | | | | | | 5) THE DESIGNER OF THE DRAWING MUST PRINT AND SIGN | | | THEIR NAME ON THE DRAWING. FBC 107.2.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|