Plan Review Notes
Plan Review Notes For Permit 23010559
Permit Number 23010559
Review Stop P
Sequence Number 3
Notes
Date Text
2023-04-05 08:39:563RD REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23010559
 4/5/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #2 FROM THE 1ST
 REVIEW COPIED BELOW WAS NOT ADDRESSED. IF YOU HAVE
 QUESTIONS PLEASE CONTACT ME USING CONTACT INFO BELOW.
  
 2) THE SUBMITTED SPEC SHEET FOR THE WATTS 007 DOUBLE
 CHECK VALVE ASSEMBLY DOES NOT SHOW THAT THE DEVICE
 MEETS THE LEAD-FREE REQUIREMENTS OF NSF/ANSI/CAN 61
 (0.25% MAX WEIGHTED AVERAGE LEAD CONTENT). PLEASE NOTE
 THE WPB CROSS-CONNECTION MANUAL SPECIFIES RPZ BACKFLOW
 PREVENTERS FOR POTABLE WATER SERVICES TO MOST
 COMMERCIAL HIGH HAZARD OCCUPANCIES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  