Plan Review Notes
Plan Review Notes For Permit 23010559
Permit Number 23010559
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-18 07:13:501ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23010559
 1/18/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A BASIC SITE PLAN SHOWING THE LOCATION OF
 THE BACKFLOW PREVENTER- SEC. 107.2.1 WPB.
  
 2) THE SUBMITTED SPEC SHEET FOR THE WATTS 007 DOUBLE
 CHECK VALVE ASSEMBLY DOES NOT SHOW THAT THE DEVICE
 MEETS THE LEAD-FREE REQUIREMENTS OF NSF/ANSI/CAN 61
 (0.25% MAX WEIGHTED AVERAGE LEAD CONTENT). PLEASE NOTE
 THE WPB CROSS-CONNECTION MANUAL SPECIFIES RPZ BACKFLOW
 PREVENTERS FOR POTABLE WATER SERVICES TO MOST
 COMMERCIAL HIGH HAZARD OCCUPANCIES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  