| 2023-01-17 15:40:17 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 23010460 2000 PALM BEACH LAKES BLVD # 100 |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PLEASE PROVIDE OVERVIEW OF BUILDING SHOWING |
| | LOCATIONS AND ROUTING/ACCESS TO COMMON RESTROOMS AND |
| | DRINKING FOUNTAIN. INCLUDE ACCESSIBILITY. FBC PL 403.1, |
| | 403.3.3, 403.5, FBC ACC 202.4 |
| | |
| | 2. P0.1/ IWH PUBLIC LAVATORY DETAIL: DETAIL DOES NOT |
| | ADDRESS HOT/TEMPERED WATER TO SINKS. PROVIDE AND |
| | SPECIFY A TEMPERATURE-ACTUATED MIXING VALVE CONFORMING |
| | TO ASSE 1017 AT EACH WATER HEATER SERVICING THE SINKS. |
| | FBC PL 607.1.1, 613.1 |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |