| 2023-01-17 14:21:28 | 1ST REVIEW FMC |
| | PERMIT: 23010460 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M6.1 UNDER THE HEAT PUMP SCHEDULE LISTS THE |
| | OUTDOOR AIR BEING SUPPLIED BY EACH WSHP. PROVIDE THE |
| | OUTDOOR AIR CALCULATIONS FOR EACH USE OF SPACE IN THIS |
| | TENANT SPACE. |
| | |
| | 2) SHEET M2.1: SHOWS A 12 X 12 OUTDOOR AIR DUCT. NOTE 2 |
| | INDICATES THAT THIS DUCT WORK TO BE ROUTED BACK TO |
| | EXISTING MECHANICAL ROOM. PROVIDE DETAIL DRAWINGS FOR |
| | WHERE THIS DUCT IS LOCATED IN THE MECHANICAL ROOM. IS |
| | THIS OUTDOOR AIR CONDITIONED BEFORE IT ENTERS THE |
| | TENANT SPACE? IF NOT PROVIDE THE MECHANICAL EQUIPMENT |
| | SIZING CALCULATIONS THAT SHOW THIS UNCONDITIONED AIR |
| | BEING BROUGHT INTO THIS TENANT SPACE UNTREATED. SHOW |
| | THAT THE WSHP???S WERE SIZED WITH THIS DESIGN IN MIND |
| | AS THIS IS NOT THE TYPICAL INSTALLATION. FBC 107.3.5 |
| | |
| | 3) PLEASE SHOW THE SMOKE DETECTION SYSTEM FOR THESE |
| | WSHP IN THE TENANT SPACE. FMC 606.2.2 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |