| Date |
Text |
| 2023-04-07 13:46:45 | 1ST REVIEW FMC |
| | PERMIT: 23010434 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE BATHROOM EXHAUST SHALL MEET FMC TABLE 403.3.1.1 |
| | WHICH IS 50 CFM PER WATER CLOSET OR URINAL IF THE FAN |
| | RUNS CONTINUOUSLY WHILE OCCUPIED OR 70 CFM PER WATER |
| | CLOSET OR URINAL IF THE FAN RUNS INTERMITTENTLY. PLEASE |
| | SPECIFY THE DESIGN OF THE EXHAUST FAN FOR THE |
| | BATHROOMS. ALSO, THE CFM???S REQUIRED IF THE FAN RUNS |
| | CONTINUOUSLY IS 750 CFM. EF-2 IS 700 CFM PLEASE MAKE |
| | SURE THE EF-2 MEETS THE MINIMUM EXHAUST REQUIREMENTS |
| | FOR THE BATHROOM EXHAUST. |
| | |
| | 2) THIS COMMENT WAS NOT ADDRESSED IN THE FIRST CYCLE |
| | RESUBMITTAL: PROVIDE DETAILS FOR THE WARMING KITCHEN, |
| | INCLUDE ALL COOKING AND WARMING APPLIANCES. FBC 107.3.5 |
| | |
| | 3) THE OUTDOOR AIR CALCULATION SHOULD BE ADJUSTED FOR |
| | THE CORRECTED OCCUPANT COUNT TAKEN FROM FMC TABLE |
| | 403.3.1.1 AND NOT THE ARCHITECT???S OCCUPANT COUNT. FMC |
| | 403.3.1.1 3RD SENTENCE. |
| | |
| | CLASSROOM SHOULD BE 8 OCCUPANTS |
| | MULTIPURPOSE ASSEMBLY SHOULD BE 66 OCCUPANTS |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |