| 2023-04-05 16:26:46 | COMMUNITY CENTER |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE SHOW THE AREA INCREASE CALCULATIONS - FBC |
| | 506.2.1 - DRAWING LS1.1.0 - BUILDING CODE ANALYSIS - |
| | FOR A NON SEPARATED OCCUPANCY THE ALLOWABLE AREA FOR AN |
| | OCCUPANCY A3 OR 4 IS (24000) - FBC 508.3.2 ALLOWABLE |
| | BUILDING AREA AND HEIGHT. THE ALLOWABLE BUILDING AREA |
| | AND HEIGHT OF THE BUILDING OR PORTION THEREOF SHALL BE |
| | BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE |
| | OCCUPANCY GROUPS UNDER CONSIDERATION FOR THE TYPE OF |
| | CONSTRUCTION OF THE BUILDING IN ACCORDANCE WITH SECTION |
| | 503.1. |
| | |
| | 2) DRAWING LS1.1.0 - BUILDING CODE ANALYSIS - THE |
| | DRAWINGS SHOW A GYMNASIUM WITH SPECTATOR SEATING - |
| | SHOULD BE AN OCCUPANCY CLASSIFICATION A4 |
| | |
| | 3) IF CHANGING THE BUILDING CONSTRUCTION TYPE - THE |
| | BUILDING SET BACKS FROM THE EXISTING BUILDING SHOWN ON |
| | DRAWING SP-1 WILL NEED TO BE EVALUATED FOR FIRE RATINGS |
| | - FBC CHAPTER 6 |
| | |
| | 4) "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS" |
| | THE FORM ON PAGE 6 FOR THE THRESHOLD INSPECTOR NEEDS TO |
| | BE FILLED OUT - THE FORM ON PAGE 8 NEEDS TO BE FILLED |
| | OUT FOR THE CONTRACTOR. |
| | |
| | 5) THE STRUCTURAL DRAWINGS DO NOT SHOW AS DIGITALLY |
| | SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN |
| | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED |
| | TO BE USED IN ELECTRONIC PLAN REVIEW. (A |
| | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED |
| | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF |
| | E-SIGNATURE). |
| | |
| | |
| | |
| | |