| 2023-02-22 06:48:30 | 1ST REVIEW FMC |
| | PERMIT: 23010432 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT |
| | THE KITCHEN HOODS AND ALL GREASE DUCT WILL REQUIRE A |
| | SEPARATE PERMIT APPLICATION AND A SEPARATE REVIEW AS IT |
| | WILL NOT BE REVIEWED UNDER THIS PERMIT. |
| | |
| | 2) PROVIDE THE ENERGY CALCULATIONS. FEC C402.1 |
| | |
| | 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. FEC C403.2.1 |
| | |
| | 4) ADD A NOTE ON THE DRAWING THAT THIS BUILDING WILL |
| | NEED TO MEET THE COMMERCIAL BUILDING COMMISSIONING |
| | REQUIREMENTS OF FEC C408. FEC C401.2.1 |
| | |
| | 5) SHEET M1.0.1: PLEASE UPDATE THE MULTIPURPOSE |
| | ASSEMBLY OCCUPANCY OUTDOOR AIR CFM???S FOR RTU-1. DOING |
| | THE CALCULATION USING THE OCCUPANCY DENSITY FROM TABLE |
| | 403.3.1.1 FOR THE 1580 SQ. FT. I GET 190 OCCUPANTS. |
| | THIS INCREASES THE OUTDOOR AIR FOR THIS AREA TO 1045 |
| | CFM???S. |
| | |
| | 6) SHEET M1.0.1: RTU-5; THE MULTIPURPOSE ASSEMBLY AREA |
| | WOULD HAVE 216 OCCUPANTS WITH A TOTAL OF 1188 CFM???S |
| | OF OUTDOOR AIR REQUIRED FOR THIS SPACE. |
| | |
| | 7) SHEET M1.0.1: RTU-5; THE KITCHEN COOKING AREA IS |
| | MISSING THE PEOPLE BREATHING ZONE PART OF THE EQUATION. |
| | MINIMUM OF 12 PEOPLE FOR THIS AREA AND A TOTAL OF |
| | OUTDOOR AIR IS 157 CFM???S REQUIRED. |
| | |
| | 8) SHEET M1.2.1: THE RETURN IN THE KITCHEN WILL NEED TO |
| | MEET THE 10 FEET FROM THE HOOD REQUIREMENT IN FMC 601.5 |
| | 2ND EXCEPTION NUMBER 1. |
| | |
| | 9) SHEET M1.2.1: PLAN NOTE 4 INDICATES AN EXHAUST FAN |
| | EF 1-5, THIS EF 1-5 IS NOT ON THE EXHAUST FAN SCHEDULES |
| | ON SHEET 1.0.1. |
| | |
| | 10) SHEET M1.2.1: PLAN NOTE 3 INDICATES AN EXHAUST FAN |
| | EF 1-6, THIS EF 1-6 IS NOT ON THE EXHAUST FAN SCHEDULES |
| | ON SHEET 1.0.1 |
| | |
| | 11) ALL MECHANICAL EQUIPMENT ON THE ROOF WILL NEED TO |
| | MEET THE 10 FEET FROM THE ROOF EDGE OR PROVIDE GUARD |
| | PROTECTION ACCORDING TO FMC 304.11 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |