| 2023-01-30 16:10:53 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE 2017 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 23010432 1501 N AUSTRALIAN AVE |
| | |
| | |
| | 1ST REVIEW |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | |
| | A. PER WPB FBC 107.2.1, 107.3.5.1.5, PROVIDE THE |
| | FOLLOWING: |
| | |
| | 1. INDICATE ON THE PLANS THE TYPE OF GAS; NATURAL OR |
| | LP. |
| | |
| | 2. INCLUDE ON THE RISER DIAGRAM THE FOLLOWING: |
| | ***A) LOCATIONS OF VALVES (INCLUDING EMERGENCY SHUTOFF |
| | VALVE) AND REGULATORS; FBC FG 401.1 |
| | ***B) SUPPLY PRESSURE AND SYSTEM PRESSURES BETWEEN |
| | REGULATORS; FBC FG 402.1 |
| | ***C) INCLUDE PIPE LENGTHS, APPLIANCE ID, BTU LOADS, |
| | MATERIALS AND DISTANCES TO THE APPLIANCES THAT WERE |
| | USED TO CALCULATE MINIMUM PIPE SIZES USING THE SIZING |
| | TABLES FROM FBC FG 402.4; INCLUDE REFERENCES TO THE |
| | SPECIFIC TABLE(S). FBC FG 402.4.1, 402.4.2, 402.4.3 |
| | |
| | 3. PROVIDE AN EQUIPMENT SCHEDULE; LIST THE BTU LOAD OF |
| | EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| | |
| | 4. PROVIDE ON FLOOR PLAN THE ID AND LOCATION OF |
| | APPLIANCE AND CORRESPONDING BTU LOAD. |
| | |
| | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | COOKING LINE AND SHOW HOW IT IS PROVIDED. FBC FG 304.1 |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |