| Date |
Text |
| 2023-03-01 12:36:08 | COMMUNITY CENTER |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) SEPARATE PERMIT REQUIRED FOR - EXISTING BUILDING |
| | DEMOLITION, FENCES, SITE WALLS, TENNIS COURTS, SHADE |
| | STRUCTURES, SITE LIGHTING AND PARKING LOTS. |
| | |
| | 2) PLEASE PROVIDE THE FOLLOWING STATEMENT ON THE |
| | ARCHITECTURAL DRAWINGS - THRESHOLD BLDG. REQUIRED |
| | STATEMENT: W.P.B. AMENDMENT 110.8.4.4 ALL PLANS FOR THE |
| | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| | 633 FLORIDA STATUTES. |
| | |
| | 3) PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER |
| | THE "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS". |
| | YOU CAN E MAIL ME AND ASK FOR A COPY. |
| | |
| | 4) PLEASE PROVIDE A THRESHOLD INSPECTION PLAN FBC WPB |
| | 110.8.1 |
| | |
| | 5) THE PROVIDED PRODUCT APPROVAL (FL17682-R6) - ON THE |
| | FRONT PAGE OF THE PRODUCT APPROVAL UNDER "STATUS" IT |
| | SAYS "PENDING FBC APPROVAL" STATUS NEEDS TO SAY |
| | "APPROVED". |
| | |
| | 6) DRAWINGS COV-1, GN-1, DM-1, DM-2, DM-3, PGD-1, |
| | PGD-2, PGD-3, UT-1, UT-2, UT-3, DET-1, DET-2, DET-3, |
| | HD-1, HD-2, HD-3, HD-4, LT-1, LT-2, LT-3 DO NOT SHOW AS |
| | DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED |
| | DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |
| | |