Plan Review Notes
Plan Review Notes For Permit 23010427
Permit Number 23010427
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2023-03-29 14:13:26THE PREVIOUS FIRE COMMENT HAS NOT BEEN SPECIFICALLY
 ADDRESSED BY RESPONSE PROVIDED ON THE RESUBMITTAL.
  
 THE INDICATED PERMIT # DOES NOT DIRECTLY INCLUDE THE
 ANSWER TO THE SPECIFIC QUESTION FIRE PROVIDED.
  
 PLEASE PROVIDE A SPECIFIC AND DIRECT RESPONSE TO THE
 COMMENT.
  
 PREVIOUS FIRE COMMENTS ARE REPOSTED BELOW:
  
  
 *******************************************************
 *******************************************************
 ******************
  
  
 1) THERE ARE INDICATIONS OF THE DUCT WORK PASSING
 THROUGH SEVERAL WALLS; HOWEVER, THERE ARE NO
 INDICATIONS THAT THESE WALLS ARE FIRE RATED WALLS.
  
 PER NFPA 96
  
 7.7.1 DUCT ENCLOSURES.
  
 7.7.1.1 IN ALL BUILDINGS WHERE VERTICAL FIRE BARRIERS
 ARE PEN ETRATED, THE DUCTS SHALL BE ENCLOSED IN A
 CONTINUOUS ENCLOSURE
 EXTENDING FROM THE FIRST PENETRATED FIRE BARRIER AND
 ANY SUBSE QUENT FIRE BARRIERS OR CONCEALED SPACES TO OR
 THROUGH THE
 EXTERIOR, TO MAINTAIN THE FIRE RESISTANCE RATING OF THE
 HIGHEST FIRE BARRIER PENETRATED
  
  
 FOR THE OFFICIAL RECORD PLEASE PROVIDE THAT WALL
 DETAILS AND IF THEY ARE RATED OR NOT.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  