| 2023-01-17 16:11:49 | 1ST REVIEW FMC |
| | PERMIT: 23010427 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) NOT ENOUGH INFORMATION SUBMITTED TO REVIEW THIS |
| | HOOD. |
| | 2) WHY IS THE HOOD BEING INSTALLED? |
| | 3) WHAT IS THE CURRENT TENANT IN THIS SPACE? |
| | 4) WHAT IS THE OCCUPANCY OF THIS TENANT SPACE? |
| | 5) WHAT IS THE COOKING APPLIANCE THAT IS TO BE UNDER |
| | THIS HOOD? |
| | 6) IS THERE ANY FIRE RATED WALLS THAT ARE BEING |
| | PENETRATED BY THE MAKE UP AIR OR GREASE DUCT? |
| | 7) IS THERE ANY COMBUSTIBLE MATERIAL WITHIN 18??? OF |
| | THE HOOD OR GREASE DUCT? |
| | 8) PROVIDE A SITE PLAN SHOULD LOT LINES WHERE THE |
| | EXHAUST AND MAKE-UP AIR TERMINATIONS ARE LOCATED. |
| | 9) PROVIDE THE MECHANICAL SYSTEMS CALCULATIONS SHOWING |
| | THE 240 CFM???S OF MAKE UP AIR FOR THE HOOD MAKE UP AIR |
| | DESIGN. |
| | 10) THIS IS NOT A COMPLETE LIST BUT RATHER A LIST FOR |
| | THE DESIGNER TO UNDERSTAND THE TRAIN OF THOUGHT OF THIS |
| | REVIEWER. PLEASE SUBMIT A COMPLETE DESIGN FOR THIS |
| | PROJECT. FBC 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |