| Plan Review Notes For Permit 23010427 |
| Permit Number |
23010427 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-17 12:02:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF THE DUCT WORK PASSING | | | THROUGH SEVERAL WALLS; HOWEVER, THERE ARE NO | | | INDICATIONS THAT THESE WALLS ARE FIRE RATED WALLS. | | | | | | PER NFPA 96 | | | | | | 7.7.1 DUCT ENCLOSURES. | | | | | | 7.7.1.1 IN ALL BUILDINGS WHERE VERTICAL FIRE BARRIERS | | | ARE PEN ETRATED, THE DUCTS SHALL BE ENCLOSED IN A | | | CONTINUOUS ENCLOSURE | | | EXTENDING FROM THE FIRST PENETRATED FIRE BARRIER AND | | | ANY SUBSE QUENT FIRE BARRIERS OR CONCEALED SPACES TO OR | | | THROUGH THE | | | EXTERIOR, TO MAINTAIN THE FIRE RESISTANCE RATING OF THE | | | HIGHEST FIRE BARRIER PENETRATED | | | | | | | | | FOR THE OFFICIAL RECORD PLEASE PROVIDE THAT WALL | | | DETAILS AND IF THEY ARE RATED OR NOT. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|