| Plan Review Notes For Permit 23010360 |
| Permit Number |
23010360 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-04-03 10:41:18 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: PASSED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE DISCONNECTING MEANS FOR A/C EQUIPMENT (MINI | | | SPLIT OUTSIDE CONDENSER) PER NEC 440.14 OR IRC E4101.5 | | | DISCONNECTING MEANS IS REQUIRED TO BE LOCATED WITHIN | | | SIGHT FROM AND READILY ACCESSIBLE FROM THE | | | AIR-CONDITIONING EQUIPMENT. | | | | | | 2. SERVICE RECEPTACLE PER NEC 210.63 OR IRC E3901.11 | | | THE RECEPTACLE MUST BE IN A READILY ACCESSIBLE LOCATION | | | FROM THE EQUIPMENT AND MUST BE GFCI-PROTECTED AS | | | APPLICABLE TO OUTDOOR RECEPTACLES AT DWELLING | | | OCCUPANCIES | | | | | | END OF COMMENTS | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|