| 2023-03-21 16:35:48 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II/INSPECTOR |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 1.) FBC B 107.2.1, THE NEW DETAILS FOR THE TYPICAL |
| | EXTERIOR WALL ON PLAN SHEET A-1 ARE NOT CLEAR AS TO THE |
| | HOLD DOWN CONNECTION OF BOTTOM PLATE TO WOOD FRAMING |
| | AND/OR FOUNDATION BELOW. PLEASE PROVIDE THIS |
| | INFORMATION. |
| | |
| | |
| | |
| | 2.) BUILDING REVIEW APPROVAL IS ALSO PENDING APPROVAL |
| | OF SIGNATURE REVIEW. |
| | |
| | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| | |
| | THE ARCHITECT'S SIGNATURE ON PLAN SHEET A-1 DOES NOT |
| | APPEAR TO BE 3RD PARTY VERIFIABLE. |
| | |
| | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND |
| | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A |
| | VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND |
| | SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A |
| | VALID DIGITAL SIGNATURE. |
| | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR |
| | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH |
| | 61G1-16 AND 61G15, F.A.C. |
| | |
| | 2. SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE. |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. |
| | 481, F.S. & 61G1. |
| | |