| 2023-01-23 13:58:39 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE NOA NO.: |
| | 18-0717.05 COVERS MULTIPLE DESIGN PRESSURE |
| | APPLICATIONS. PLEASE SELECT APPLICATION TO BE USED FROM |
| | TABLE 2 PAGES #7-10. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. SIGNED AND SEALED NAILING |
| | CALCULATIONS MAY BE REQUIRED. |
| | 2. SUBMITTED PRODUCT APPROVAL FL14207-R27 HAS BEEN |
| | REVISED TO FL14207-R28. PROVIDE THE FOLLOWING: COVER |
| | PAGE, EVALUATION REPORTS PAGES 1-5 TO INCLUDE |
| | LIMITATIONS PAGE(S) AND INSTALLATION INSTRUCTIONS FOR |
| | SYSTEM USED. |
| | 3. FBC B 1609 PROVIDE A COMPLETE SET OF SIGNED AND |
| | SEALED ENGINEERED DESIGN PRESSURE CALCULATIONS BY A |
| | FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT, OR REGISTERED ROOF CONSULTANT OR PROVIDE |
| | PAGE NUMBER FROM MASTER PLANS WERE INFORMATION CAN BE |
| | FOUND. |
| | 4. FBC B 107.3.4.1. SUBMIT ALL PRODUCT |
| | APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING |
| | PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST |
| | BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE |
| | SUBMITTING. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |