Plan Review Notes
Plan Review Notes For Permit 23010335
Permit Number 23010335
Review Stop M
Sequence Number 1
Notes
Date Text
2023-01-11 14:52:421) PROVIDE A SITE PLAN SHOWING WHICH STRUCTURE THE
 MECHANICAL WORK IS BEING INSTALLED.
  
 2) PROVIDE THE ENERGY CALCULATION. FRC R101.5.1.1.1
  
 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FRC R403.7.1
  
 4) SHOW THE ACCESS FOR THE AHU SERVICING. FRC M1305.1
  
 5) THE DESIGNER OF THE DRAWING MUST PRINT AND SIGN
 THEIR NAME. FBC 107.2.1
  