| Plan Review Notes For Permit 23010315 |
| Permit Number |
23010315 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-24 10:26:23 | SEE GAS REVIEWER'S COMMENTS BELOW: | | | | | | 1ST REVIEW FBC-2020 RES. GAS | | | REVISIONS TO PERMIT- 23010312 & 23010315 | | | 2/2/2023 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS G-1, M-1, & M-2: THE MAKEUP AIR DUCT FOR THE | | | RANGE EXHAUST SHALL NOT BE USED TO PROVIDE COMBUSTION | | | AIR FOR THE NEW RANGE IN THE ACCESSORY STRUCTURE- | | | G2407.1 FBC RES. EXCEPTION 1 UNDER G2407.1 APPLIES ONLY | | | TO DRYERS. IF THE INTENTION IS TO PROVIDE A DUCT TO | | | SUPPLY THE ADDITIONAL COMBUSTION AIR FOR THE RANGE NOT | | | PROVIDED BY THE INDOOR AIR VOLUME, PLEASE REFER TO | | | G2407.7 AND SHOW COMPLIANCE WITH G2407.7- G2407.7.3. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|