| Plan Review Notes For Permit 23010262 |
| Permit Number |
23010262 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-06-08 17:04:22 | 3RD REVIEW FBC-2020 RES. GAS | | | PERMIT- 23010262 | | | 6/8/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | COMMENT #3 FROM THE PREVIOUS REVIEW STILL EXISTS. | | | COMBUSTION AIR CALCULATIONS FOR THE NEW RANGES AND OVEN | | | NOT PROVIDED. | | | | | | 3) PLEASE NOTE THAT COMBUSTION AIR AND VENTING PLANS | | | ARE REQUIRED FOR INTERIOR APPLIANCES SUCH AS RANGES, | | | OVENS, COOKTOPS, DRYERS, FIREPLACES ETC.- SEC. | | | 107.3.5.3 WPB. | | | | | | NEW COMMENT BASED ON RESUBMITTED PLAN. | | | | | | 1) SHEET P-1: IT APPEARS THE LOCATIONS OF THE TANKLESS | | | WATER HEATERS ARE NOT IN COMPLIANCE WITH SEC. G2427.8 | | | FBC RES. THE VENTS FROM THE WATER HEATERS SHALL | | | TERMINATE NOT LESS THAN 4 FEET BELOW, 4 FEET | | | HORIZONTALLY FROM, OR 1 FOOT ABOVE ANY DOOR, OPERABLE | | | WINDOW OR GRAVITY AIR INLET INTO ANY BUILDING. THE | | | BOTTOM OF THE VENT TERMINAL SHALL BE LOCATED NOT LESS | | | THAN 12 INCHES ABOVE FINISHED GROUND LEVEL. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|