| 2023-06-13 12:57:42 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE EXTERIOR WINDOWS, DOORS AND |
| | ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD |
| | FBC WPB 107.3.4 |
| | |
| | 2) DRAWING A1.0 IN THE "ZONING INFORMATION" CHART THE |
| | FLOOR ELEVATION IS NOT THE SAME AS THE FLOOR ELEVATION |
| | SHOWN ON THE PLAN. AND THE FLOOD ZONE INFORMATION SHOWS |
| | 9.00 NAVD AND THE PLAN VIEW SHOWS 10.00 NAVD |
| | |
| | 3) PLEASE PROVIDE A SOIL REPORT - FBC R401.4 |
| | |
| | 4) PLEASE PROVIDE THE FLOOD VENT CERTIFICATIONS (ICC |
| | EVALUTATION - PRODUCT APPROVALS) FBC R322.2.2 |
| | |
| | 5) DRAWING A3.0 SHOWS 4 FLOOD VENTS FOR THE GARAGE AT |
| | 200 SQ FOOT RATING EACH - NOT ENOUGH FLOOD VENTS FOR A |
| | GARAGE WITH 898 SQ. FT. FBC R322.2.2 |
| | |
| | 6) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE - |
| | FBC 107.3.5.3 |
| | |
| | 7) PLEASE SHOW THE STORM WATER FLOW AWAY FROM THE |
| | BUILDING AND AWAY FROM THE ADJACENT PROPERTY ON THE |
| | SITE PLAN OR PROVIDE A STORM WATER DRAINAGE PLAN - FBC |
| | WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS |
| | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| | AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED |
| | WATER RETAINING SWALES) |
| | |
| | 8) PLEASE PROVIDE DOCUMENTATION (ICC EVALUATION REPORT) |
| | FOR THE FOAM SPRAY INSULATION - FBC R316.3 |
| | |
| | 9) PLEASE PROVIDE A SURVEY SHOWING THE PLACEMENT OF THE |
| | BUILDING, FLOOD ZONES AND THE FLOOD ZONE DELINEATION |
| | LINE BETWEEN THE FLOOD ZONES. |
| | |
| | 10) EXTERIOR WINDOW, DOOR AND ROOFING SYSTEM PRODUCT |
| | APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS |
| | TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - FBC |
| | WPB107.3.4.1 |
| | |
| | |
| | |
| | |
| | |
| | |