Plan Review Notes
Plan Review Notes For Permit 23010262
Permit Number 23010262
Review Stop P
Sequence Number 2
Notes
Date Text
2023-04-13 17:16:482ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23010262
 4/13/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1.0 PLUMBING RISER: THE HORIZONTAL WET VENTS
 IN HIS BATH ANS BATH #5 ARE NOT DESIGNED IN ACCORDANCE
 WITH SEC. P3108.2.1 FBC RES- NO MORE THAN ONE WET
 VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE
 DRY-VENTED FIXTURE DRAIN CONNECTION AT THE LAVATORIES.
  
 2) 2ND REQUEST SHEET A6.0: PLEASE PROVIDE ADDITIONAL
 ROOF DRAINAGE INFORMATION ON THE PLAN INCLUDING
 LOCATIONS AND SIZES OF OVERFLOW DRAINS OR SCUPPERS-
 SEC. R903.4.1 FBC RES.
  
 A) THE PLAN HAS A NOTE REFERRING TO SHOP DRAWINGS FOR
 THE ROOF DRAINAGE SYSTEM. THE DRAWINGS REQUIRE THE
 APPROVAL STAMP OF THE ARCHITECT OF RECORD AND CAN BE
 SUBMITTED NOW FOR REVIEW OR BE A DEFERRED SUBMITTAL-
 SEC. 107.3.4.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  