| Plan Review Notes For Permit 23010262 |
| Permit Number |
23010262 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-13 17:16:48 | 2ND REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 23010262 | | | 4/13/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A1.0 PLUMBING RISER: THE HORIZONTAL WET VENTS | | | IN HIS BATH ANS BATH #5 ARE NOT DESIGNED IN ACCORDANCE | | | WITH SEC. P3108.2.1 FBC RES- NO MORE THAN ONE WET | | | VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE | | | DRY-VENTED FIXTURE DRAIN CONNECTION AT THE LAVATORIES. | | | | | | 2) 2ND REQUEST SHEET A6.0: PLEASE PROVIDE ADDITIONAL | | | ROOF DRAINAGE INFORMATION ON THE PLAN INCLUDING | | | LOCATIONS AND SIZES OF OVERFLOW DRAINS OR SCUPPERS- | | | SEC. R903.4.1 FBC RES. | | | | | | A) THE PLAN HAS A NOTE REFERRING TO SHOP DRAWINGS FOR | | | THE ROOF DRAINAGE SYSTEM. THE DRAWINGS REQUIRE THE | | | APPROVAL STAMP OF THE ARCHITECT OF RECORD AND CAN BE | | | SUBMITTED NOW FOR REVIEW OR BE A DEFERRED SUBMITTAL- | | | SEC. 107.3.4.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|