Plan Review Notes
Plan Review Notes For Permit 23010262
Permit Number 23010262
Review Stop B
Sequence Number 2
Notes
Date Text
2023-04-18 13:59:56NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS DO NOT APPEAR TO BE COMPLETE - DRAWINGS
 HAVE A NOTE ON THEM THAT SAYS - "PROGRESS SET NOT FOR
 CONSTRUCTION" - CANNOT HAVE THIS STATEMENT ON THE
 DRAWINGS.
  
 2) STRUCTURAL DRAWINGS ARE MISSING FROM PROJECTDOX.
  
 3) DRAWING INDEX ON DRAWING A0.0 DOES NOT MATCH THE
 DRAWINGS UPLOADED TO PROJECTDOX.
  
 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD
 FBC WPB 107.3.4
  
 5) DOOR AND WINDOW SCHEDULES ARE INCOMPLETE - PLEASE
 SHOW ALL WINDOW AND DOOR SIZES.
  
 6) PLEASE SHOW THE EMERGENCY EGRESS WINDOW SIZES FROM
 BEDROOM 6 AND 7 - FBC R310.1
  
 7) PLEASE SHOW THE WINDOW SILL HEIGHTS - R312.2.1
 WINDOW SILLS.
 IN DWELLING UNITS, WHERE THE TOP OF THE SILL OF AN
 OPERABLE WINDOW OPENING IS LOCATED LESS THAN 24 INCHES
 (610 MM) ABOVE THE FINISHED FLOOR AND GREATER THAN 72
 INCHES (1829 MM) ABOVE THE FINISHED GRADE OR OTHER
 SURFACE BELOW ON THE EXTERIOR OF THE BUILDING, THE
 OPERABLE WINDOW SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1.OPERABLE WINDOWS WITH OPENINGS THAT WILL NOT ALLOW A
 4-INCH-DIAMETER (102 MM) SPHERE TO PASS THROUGH THE
 OPENING WHERE THE OPENING IS IN ITS LARGEST OPENED
 POSITION.
 2.OPERABLE WINDOWS THAT ARE PROVIDED WITH WINDOW FALL
 PREVENTION DEVICES THAT COMPLY WITH ASTM F2090.
 3.OPERABLE WINDOWS THAT ARE PROVIDED WITH WINDOW
 OPENING CONTROL DEVICES THAT COMPLY WITH SECTION - FBC
 R312.2.2.
  
 8) PLEASE PROVIDE A SOIL REPORT - FBC R401.4
  
 9) PLEASE SHOW GUARD RAIL DETAILS - HEIGHT, OPENING,
 ATTACHMENTS ETC. - FBC R312.1
  
 10) PLEASE SHOW THE ROOF OVERFLOW DRAINAGE TYPE, AND
 LOCATION - FBC R903.4.1
  
 11) PLEASE SHOW THE REQUIRED FLOOD VENTS - LOCATION AND
 SIZES - FOR THE GARAGE BELOW THE DESIGN FLOOD ELEVATION
 - FBC R322.2.2
  
 12) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE -
 FBC 107.3.5.3
  
 13) PLEASE SHOW THE STORM WATER FLOW AWAY FROM THE
 BUILDING AND AWAY FROM THE ADJACENT PROPERTY ON THE
 SITE PLAN OR PROVIDE A STORM WATER DRAINAGE PLAN - FBC
 WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 14) PLEASE PROVIDE DOCUMENTATION FOR THE FOAM SPRAY
 INSULATION - FBC R316.3
  
 15) PLEASE PROVIDE A SURVEY SHOWING THE PLACEMENT OF
 THE BUILDING, FLOOD ZONES AND THE FLOOD ZONE
 DELINEATION LINE BETWEEN THE FLOOD ZONES.
  
 16) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 DESIGNER FBC WPB 107.1 - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
  
  
  