| 2023-04-18 13:59:56 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWINGS DO NOT APPEAR TO BE COMPLETE - DRAWINGS |
| | HAVE A NOTE ON THEM THAT SAYS - "PROGRESS SET NOT FOR |
| | CONSTRUCTION" - CANNOT HAVE THIS STATEMENT ON THE |
| | DRAWINGS. |
| | |
| | 2) STRUCTURAL DRAWINGS ARE MISSING FROM PROJECTDOX. |
| | |
| | 3) DRAWING INDEX ON DRAWING A0.0 DOES NOT MATCH THE |
| | DRAWINGS UPLOADED TO PROJECTDOX. |
| | |
| | 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE EXTERIOR WINDOWS, DOORS AND |
| | ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD |
| | FBC WPB 107.3.4 |
| | |
| | 5) DOOR AND WINDOW SCHEDULES ARE INCOMPLETE - PLEASE |
| | SHOW ALL WINDOW AND DOOR SIZES. |
| | |
| | 6) PLEASE SHOW THE EMERGENCY EGRESS WINDOW SIZES FROM |
| | BEDROOM 6 AND 7 - FBC R310.1 |
| | |
| | 7) PLEASE SHOW THE WINDOW SILL HEIGHTS - R312.2.1 |
| | WINDOW SILLS. |
| | IN DWELLING UNITS, WHERE THE TOP OF THE SILL OF AN |
| | OPERABLE WINDOW OPENING IS LOCATED LESS THAN 24 INCHES |
| | (610 MM) ABOVE THE FINISHED FLOOR AND GREATER THAN 72 |
| | INCHES (1829 MM) ABOVE THE FINISHED GRADE OR OTHER |
| | SURFACE BELOW ON THE EXTERIOR OF THE BUILDING, THE |
| | OPERABLE WINDOW SHALL COMPLY WITH ONE OF THE FOLLOWING: |
| | 1.OPERABLE WINDOWS WITH OPENINGS THAT WILL NOT ALLOW A |
| | 4-INCH-DIAMETER (102 MM) SPHERE TO PASS THROUGH THE |
| | OPENING WHERE THE OPENING IS IN ITS LARGEST OPENED |
| | POSITION. |
| | 2.OPERABLE WINDOWS THAT ARE PROVIDED WITH WINDOW FALL |
| | PREVENTION DEVICES THAT COMPLY WITH ASTM F2090. |
| | 3.OPERABLE WINDOWS THAT ARE PROVIDED WITH WINDOW |
| | OPENING CONTROL DEVICES THAT COMPLY WITH SECTION - FBC |
| | R312.2.2. |
| | |
| | 8) PLEASE PROVIDE A SOIL REPORT - FBC R401.4 |
| | |
| | 9) PLEASE SHOW GUARD RAIL DETAILS - HEIGHT, OPENING, |
| | ATTACHMENTS ETC. - FBC R312.1 |
| | |
| | 10) PLEASE SHOW THE ROOF OVERFLOW DRAINAGE TYPE, AND |
| | LOCATION - FBC R903.4.1 |
| | |
| | 11) PLEASE SHOW THE REQUIRED FLOOD VENTS - LOCATION AND |
| | SIZES - FOR THE GARAGE BELOW THE DESIGN FLOOD ELEVATION |
| | - FBC R322.2.2 |
| | |
| | 12) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE - |
| | FBC 107.3.5.3 |
| | |
| | 13) PLEASE SHOW THE STORM WATER FLOW AWAY FROM THE |
| | BUILDING AND AWAY FROM THE ADJACENT PROPERTY ON THE |
| | SITE PLAN OR PROVIDE A STORM WATER DRAINAGE PLAN - FBC |
| | WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS |
| | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| | AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED |
| | WATER RETAINING SWALES) |
| | |
| | 14) PLEASE PROVIDE DOCUMENTATION FOR THE FOAM SPRAY |
| | INSULATION - FBC R316.3 |
| | |
| | 15) PLEASE PROVIDE A SURVEY SHOWING THE PLACEMENT OF |
| | THE BUILDING, FLOOD ZONES AND THE FLOOD ZONE |
| | DELINEATION LINE BETWEEN THE FLOOD ZONES. |
| | |
| | 16) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE |
| | DESIGNER FBC WPB 107.1 - SIGNED AND SEALED DRAWINGS IN |
| | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED |
| | TO BE USED IN ELECTRONIC PLAN REVIEW. (A |
| | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED |
| | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF |
| | E-SIGNATURE). |
| | |
| | |
| | |
| | |