2023-06-28 08:36:30NEW 2 STORY APARTMENT BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING LS-1 SHOWS THE RETAIL EXIT DOOR ON THE EAST
 SIDE INTO THE SIDE OF THE STAIR.
  
 2) THERE ARE 2 NUMBER 5 DOORS SHOWN ON THE DOOR
 SCHEDULE - DOOR NUMBER 5 FOR THE WALK IN CLOSET IS NOT
 WIDE ENOUGH (AS SHOWN ON THE DOOR SCHEDULE) FOR A
 USABLE DOOR PER FBC FHA REQUIREMENT 3
  
 3) DRAWING A-10.00 AND A-10.2 - PLEASE SHOW THE CLEAR
 FLOOR SPACE FOR THE BATH TUBS - INSIDE THE BATHROOMS -
 FBC FHA REQUIREMENT 7
  
 4) CANNOT HAVE A CURB CUT IN A RAMP LANDING - 405.4
 FLOOR OR GROUND SURFACES.
 FLOOR OR GROUND SURFACES OF RAMP RUNS SHALL COMPLY WITH
 302. CHANGES IN LEVEL OTHER THAN THE RUNNING SLOPE AND
 CROSS SLOPE ARE NOT PERMITTED ON RAMP RUNS.
  
 5) PLEASE SHOW RAMP HAND RAIL DETAILS AND SHOW HAND
 RAILS ON BOTH SIDES OF THE ACCESSIBLE RAMPS - FBC A
 505.2 WHERE REQUIRED. HANDRAILS SHALL BE PROVIDED ON
 BOTH SIDES OF STAIRS AND RAMPS.
  
 6) PLEASE SHOW THE ACCESSIBLE RAMP SLOPE - FBC A
 405.2SLOPE. RAMP RUNS SHALL HAVE A RUNNING SLOPE NOT
 STEEPER THAN 1:12.
  
 7) DRAWING A-4.2 AND A-6.00 DETAIL 1 AND 2 SHOW STAIR
 HAND RAIL AT 2' 9" - FBC 1014.2 HEIGHT.
 HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR
 FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT
 LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38
 INCHES (965 MM).
  
  
  
  
  
  
  
  
  
  