| 2023-06-28 08:36:30 | NEW 2 STORY APARTMENT BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DRAWING LS-1 SHOWS THE RETAIL EXIT DOOR ON THE EAST |
| | SIDE INTO THE SIDE OF THE STAIR. |
| | |
| | 2) THERE ARE 2 NUMBER 5 DOORS SHOWN ON THE DOOR |
| | SCHEDULE - DOOR NUMBER 5 FOR THE WALK IN CLOSET IS NOT |
| | WIDE ENOUGH (AS SHOWN ON THE DOOR SCHEDULE) FOR A |
| | USABLE DOOR PER FBC FHA REQUIREMENT 3 |
| | |
| | 3) DRAWING A-10.00 AND A-10.2 - PLEASE SHOW THE CLEAR |
| | FLOOR SPACE FOR THE BATH TUBS - INSIDE THE BATHROOMS - |
| | FBC FHA REQUIREMENT 7 |
| | |
| | 4) CANNOT HAVE A CURB CUT IN A RAMP LANDING - 405.4 |
| | FLOOR OR GROUND SURFACES. |
| | FLOOR OR GROUND SURFACES OF RAMP RUNS SHALL COMPLY WITH |
| | 302. CHANGES IN LEVEL OTHER THAN THE RUNNING SLOPE AND |
| | CROSS SLOPE ARE NOT PERMITTED ON RAMP RUNS. |
| | |
| | 5) PLEASE SHOW RAMP HAND RAIL DETAILS AND SHOW HAND |
| | RAILS ON BOTH SIDES OF THE ACCESSIBLE RAMPS - FBC A |
| | 505.2 WHERE REQUIRED. HANDRAILS SHALL BE PROVIDED ON |
| | BOTH SIDES OF STAIRS AND RAMPS. |
| | |
| | 6) PLEASE SHOW THE ACCESSIBLE RAMP SLOPE - FBC A |
| | 405.2SLOPE. RAMP RUNS SHALL HAVE A RUNNING SLOPE NOT |
| | STEEPER THAN 1:12. |
| | |
| | 7) DRAWING A-4.2 AND A-6.00 DETAIL 1 AND 2 SHOW STAIR |
| | HAND RAIL AT 2' 9" - FBC 1014.2 HEIGHT. |
| | HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR |
| | FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT |
| | LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38 |
| | INCHES (965 MM). |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |