| Plan Review Notes For Permit 23010249 |
| Permit Number |
23010249 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-04-04 13:34:45 | FIRE REVIEW COMMENTS: | | | | | | (1) INSTALL, TEST AND INSPECT ALL FIRE PROTECTION | | | UNDERGROUND SERVICES FOR FIRE HYDRANTS AND FIRE | | | SPRINKLERS PER NFPA 24, THE STANDARD FOR THE | | | INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR | | | APPURTENANCES. TO ENSURE COMPLIANCE, DO NOT COVER OVER | | | ANY JOINTS PRIOR TO INSPECTION BY A FIRE DEPARTMENT | | | REPRESENTATIVE. | | | | | | (2) THE LIFE SAFETY PLAN INDICATES THE BUILDING IS TO | | | BE EQUIPPED WITH A FIRE SPRINKLER SYSTEM AND A WET | | | STANDPIPE SYSTEM. THE FIRE PROTECTION SYSTEM | | | ENGINEERING DOCUMENTS BASED ON THE DESIGN CRITERIA BY | | | THE ENGINEER OF RECORD ARE TO BE SUBMITTED AS PART OF | | | THE MASTER PERMIT. THE LAYOUT DOCUMENTS ARE SUBMITTED | | | FOR THE FIRE SPRINKLER INSTALLATION PERMIT. FAC | | | 61G15-32.002. SEE NOTE 8, ON THE SUBMITTED LIFE SAFETY | | | PLAN. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | | | | |
|