2023-04-07 12:46:48NEW 2 STORY APARTMENT BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE EXTERIOR WALL OPENINGS PROTECTION ON
 THE SOUTH SIDE OF THE BUILDING PER FBC TABLE 705.8
 705.3 BUILDINGS ON THE SAME LOT.
 FOR THE PURPOSES OF DETERMINING THE REQUIRED WALL AND
 OPENING PROTECTION, PROJECTIONS AND ROOF-COVERING
 REQUIREMENTS, BUILDINGS ON THE SAME LOT SHALL BE
 ASSUMED TO HAVE AN IMAGINARY LINE BETWEEN THEM.
  
 2) DRAWING A-1.0 - UNDER "SCOPE OF WORK" - SAYS 2 - 3
 STORY BUILDINGS - BUILDINGS ARE 2 STORIES.
  
 3) DRAWINGS S-2.1 AND S-2.2 SHOW 3 STORY BUILDINGS -
 BUILDINGS ARE 2 STORIES.
  
 4) DRAWING LS-1 SHOWS THE RETAIL EXIT DOOR ON THE EAST
 SIDE INTO THE SIDE OF THE STAIR.
  
 5) DRAWING LS-1 SHOWS BUILDING CONSTRUCTION TYPE IIIA -
 ADDITIONAL FIRE RATINGS ARE REQUIRED THEN WHAT IS SHOWN
 ON THE DRAWING - SEE FBC TABLE 601
  
 6) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 7) PLEASE SHOW THE GRAB BAR BACKING DETAILS FOR ALL OF
 THE BATHROOMS ON THE GROUND LEVEL - FBC FHA REQUIREMENT
 6
  
 8) DOOR NUMBER 5 FOR THE WALK IN CLOSET IS NOT WIDE
 ENOUGH (AS SHOWN ON THE DOOR SCHEDULE) FOR A USABLE
 DOOR PER FBC FHA REQUIREMENT 3
  
 9) PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE BATH TUBS
 - INSIDE THE BATHROOM - FBC FHA REQUIREMENT 7
  
 10) DRAWING SP-1 - SHOWS AN ADA RAMP LEADING INTO THE
 STAIR - PLEASE SHOW THE VERTICAL CLEARANCE PROTECTION
 PER - FBC A 307.4 VERTICAL CLEARANCE.
 VERTICAL CLEARANCE SHALL BE 80 INCHES (2030 MM) HIGH
 MINIMUM. GUARDRAILS OR OTHER BARRIERS SHALL BE PROVIDED
 WHERE THE VERTICAL CLEARANCE IS LESS THAN 80 INCHES
 (2030 MM) HIGH. THE LEADING EDGE OF SUCH GUARDRAIL OR
 BARRIER SHALL BE LOCATED 27 INCHES (685 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 11) PLEASE SHOW THE ADA RAMP SLOPES AND TURNS AT THE
 BACK OF THE STAIR - FBC A 405.7.4 CHANGE IN DIRECTION.
 RAMPS THAT CHANGE DIRECTION BETWEEN RUNS AT LANDINGS
 SHALL HAVE A CLEAR LANDING 60 INCHES (1525 MM) MINIMUM
 BY 60 INCHES (1525 MM) MINIMUM.
  
 12) DRAWING A-5.1 - TWO BEDROOM UNIT PLAN - MASTER
 BEDROOM SHOWS A FRENCH DOOR WITH NO BALCONY - GUARDS
 ARE REQUIRED - FBC 1015.1
  
 13) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD - FBC 107.3.4
  
 14) PRODUCT APPROVALS MAY BE DEFERRED BY LISTING THE
 ITEMS TO BE DEFERRED ON THE DRAWINGS - FBC WPB
 107.3.4.1
  
 15) SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER
 ENCLOSURE, PARKING LOT, RETAINING WALLS
  
  