Plan Review Notes
Plan Review Notes For Permit 23010248
Permit Number 23010248
Review Stop P
Sequence Number 3
Notes
Date Text
2023-06-20 14:08:533RD REVIEW FBC-2020 PLUMBING
 PERMIT- 23010248
 6/20/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED. 3RD REQUEST FOR THE
 BACKFLOW PERMIT APPLICATION TO BE SUBMITTED. PLEASE
 COMMENT #1 BELOW AND IF YOU DON???T UNDERSTAND WHAT IS
 REQUIRED PLEASE CONTACT ME ASAP.
  
 1) AS PREVIOUSLY REQUESTED, PLEASE SUBMIT THE PERMIT
 APPLICATION FOR THE POTABLE WATER BACKFLOW PREVENTER-
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE
 WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 NEW COMMENT BASED ON RESUBMITTED PLANS.
  
 1) SHEET A1.0A WHICH IS THE FLOOR PLANS FOR A BUILDING
 WITH ADA COMPLIANCE WAS RESUBMITTED IN PLACE OF A1.0B
 WHICH IS THE FLOOR PLANS WITH NON-ADA COMPLIANCE.
 PLEASE SUBMIT THE CORRECT PLANS.
  
 2) SHEETS A10.0, A10.1: THE REQUIRED 30X48-INCH CLEAR
 FLOOR SPACE DIAGRAM FOR THE BATHTUB SHOWING A
 PERPENDICULAR APPROACH IN THE TYPE A BATHROOM WAS
 REMOVED. THIS REQUIRED CLEAR FLOOR SPACE ALSO SERVES AS
 THE MANEUVERABLE CLEARANCE BEYOND THE ARC OF THE
 INSWINGING DOOR- REFER TO EXAMPLE A BATHROOM ON PAGE
 7.36 OF THE FHDA MANUAL.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  