| 2023-05-02 08:30:15 | NEW RESIDENTIAL BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND |
| | ROOFING SYSTEM - ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD FBC WPB 107.3.4 |
| | |
| | 2) DRAWING LS-1 - UNDER "SCOPE OF WORK" - WIND DESIGN - |
| | ASCE 7-10 IS SHOWN - SHOULD BE ASCE 7-16 - FBC CHAPTER |
| | 35 |
| | |
| | 3) DRAWING A-4.2 - DETAIL 1 - SHOWS HAND RAIL HEIGHT AT |
| | 2'9" - FBC 1014.2 HEIGHT. |
| | HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR |
| | FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT |
| | LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38 |
| | INCHES (965 MM). |
| | |
| | 4) THE DRAWINGS (A-10.1) (A-10.00) (A-9.00) SHOWS THAT |
| | THE FBC ENERGY CONSERVATION NOTES USING THE 2014 CODE - |
| | SHOULD BE PER THE 2020 FBC ENERGY CONSERVATION. |
| | |
| | 5) FOR THE UNITS ABOVE THE FIRST FLOOR - THE FOLLOWING |
| | ACUSTICAL TEST REPORTS ARE REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| | CEILING DESCRIPTION) |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| | DROP CEILING DESCRIPTION) |
| | |
| | 6) ITEMS SUCH AS EXTERIOR WINDOW, DOOR, ROOFING SYSTEM |
| | PRODUCT APPROVALS AND FLOORING ACOUSTICAL REPORTS MAY |
| | BE DEFERRED SUBMITTALS BY LISTING THE DEFERRED ITEMS ON |
| | THE CONSTRUCTION DRAWINGS - FBC WPB 107.3.4.1 |
| | |
| | 7) FYI - SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER |
| | ENCLOSURE, TRELLIS, PLAYGROUND, PARKING LOT, SITE |
| | LIGHTING |