| Plan Review Notes For Permit 23010248 |
| Permit Number |
23010248 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-23 14:20:40 | 1ST REVIEW FMC | | | PERMIT: 23010248 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHOW HOW THE DRYER DUCT WILL NOT BE INSIDE OF THE | | | RETURN AIR PLENUM. FMC 504.4 | | | | | | 2) THE KITCHEN HOOD EXHAUST DUCT THAT IS RUNNING INSIDE | | | OF THE RETURN AIR PLENUM WILL NEED TO MEET THE DUCT | | | CONSTRUCTION REQUIREMENTS OF FMC 603. SPECIFY THE DUCT | | | THICKNESS WILL THE REQUIREMENTS OF FMC 603.4 | | | | | | 3) CHANGE THE PVC PIPING FOR THE CONDENSATE DRAIN AS | | | THIS MATERIAL WILL NOT MEET THE SMOKE AND FLAME SPREAD | | | REQUIREMENTS OF FMC 602.2.1.7 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|