Plan Review Notes
Plan Review Notes For Permit 23010248
Permit Number 23010248
Review Stop B
Sequence Number 1
Notes
Date Text
2023-03-09 11:00:02NEW RESIDENTIAL BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE EXTERIOR FIRE RATED DOOR TO THE
 UNITS TO BE SELF CLOSING (THE DOOR SCHEDULE MAY SHOW
 THE WRONG HARDWARE TYPE) - FBC 716.5.9 DOOR CLOSING.
 FIRE DOORS SHALL BE LATCHING AND SELF- OR
 AUTOMATIC-CLOSING IN ACCORDANCE WITH THIS SECTION.
  
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEM - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.3.4
  
 3) PLEASE SHOW THE GRAB BAR WALL REINFORCEMENT TYPE,
 SIZE AND LOCATION DIMENSIONS ( FOR THE GROUND FLOOR 2
 BEDROOM UNITS) - FBC FHA REQUIREMENT 6
  
 4) DRAWING A-1.0B - UNDER "SCOPE OF WORK" - WIND DESIGN
 - ASCE 7-10 IS SHOWN - SHOULD BE ASCE 7-16 - FBC
 CHAPTER 35
  
 5) DRAWING A-6.1 - DETAIL 1 - SHOWS HAND RAIL HEIGHT AT
 2'9" - FBC 1014.2 HEIGHT.
 HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR
 FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT
 LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38
 INCHES (965 MM).
  
 6) FOR THE UNITS ABOVE THE FIRST FLOOR - THE FOLLOWING
 ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 7) PLEASE PROVIDE THE FIRE SPRINKLER AND ALARM PLANS -
 FBC WPB 107.3.5.1.1 (5)
  
 7) SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER
 ENCLOSURE, TRELLIS, PLAYGROUND, PARKING LOT, SITE
 LIGHTING