| 2023-03-07 15:19:06 | 3RD REVIEW FMC | | | PERMIT: 23010224 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | PLEASE ADDRESS EACH COMMENT BELOW BEFORE RESUBMITTAL. | | | IF YOU HAVE ANY QUESTIONS PLEASE GIVE ME A CALL. | | | | | | | | | | | | 2) PLEASE SUBMIT OUTDOOR AIR CALCULATIONS FOR THE | | | OCCUPANT DENSITY FROM FMC TABLE 403.3.1.1 THE KITCHEN | | | EXHAUST IS ALSO LOW PLEASE RECALCULATE THESE 2 AREAS | | | USING TABLE 403.3.1.1 OCCUANCY DENSITY. | | | | | | | | | 3) ADJUST THE AIR BALANCE SCHEDULE ONCE THE REQUIRED | | | OUTDOOR AIR HAS BEEN CORRECTED. FMC 501.4 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|