Plan Review Notes
Plan Review Notes For Permit 23010224
Permit Number 23010224
Review Stop M
Sequence Number 2
Notes
Date Text
2023-02-21 06:22:472ND REVIEW FMC
 PERMIT: 23010224
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SPECS FOR THE OVENS THAT WERE ASKED FOR IN THE
 FIRST CYCLE REVIEW COMMENTS WERE NOT SUBMITTED IN THIS
 CYCLE. PROVIDE THE OVEN SPECS. AND HOW IT WOULD MEET
 THE EXCEPTION FOR NO HOOD REQUIRED ACCORDING TO FMC
 507.1 EXCEPTION NUMBER 2.
  
 2) THE OUTDOOR AIR CALCULATIONS ARE REQUIRED TO BE
 CALCULATED USING TABLE 403.3.1.1 AND NOT THE
 ARCHITECT???S EGRESS NUMBERS. PROVIDE THE OCCUPANCY FOR
 EACH SPACE THAT MOST CLOSELY RESEMBLES THE USE OF SPACE
 AND THE OCCUPANT DENSITY FOR EACH SPACE FROM TABLE
 403.3.1.1. A CORRIDOR WOULD NOT BE USED FOR A LOBBY
 AREA. THE DINING AREA WOULD BE CALCULATED FOR 79
 OCCUPANTS. I ASSUME THE SQUARE FOOTAGE GIVEN FOR EACH
 OCCUPANCY CLASSIFICATION IS IN ACCORDANCE WITH FOOTNOTE
 A OF TABLE 403.3.1.1. FMC 403.3.1.1
  
 3) ADJUST THE AIR BALANCE SCHEDULE ONCE THE REQUIRED
 OUTDOOR AIR HAS BEEN CORRECTED. FMC 501.4
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  