| 2023-02-21 06:22:47 | 2ND REVIEW FMC |
| | PERMIT: 23010224 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SPECS FOR THE OVENS THAT WERE ASKED FOR IN THE |
| | FIRST CYCLE REVIEW COMMENTS WERE NOT SUBMITTED IN THIS |
| | CYCLE. PROVIDE THE OVEN SPECS. AND HOW IT WOULD MEET |
| | THE EXCEPTION FOR NO HOOD REQUIRED ACCORDING TO FMC |
| | 507.1 EXCEPTION NUMBER 2. |
| | |
| | 2) THE OUTDOOR AIR CALCULATIONS ARE REQUIRED TO BE |
| | CALCULATED USING TABLE 403.3.1.1 AND NOT THE |
| | ARCHITECT???S EGRESS NUMBERS. PROVIDE THE OCCUPANCY FOR |
| | EACH SPACE THAT MOST CLOSELY RESEMBLES THE USE OF SPACE |
| | AND THE OCCUPANT DENSITY FOR EACH SPACE FROM TABLE |
| | 403.3.1.1. A CORRIDOR WOULD NOT BE USED FOR A LOBBY |
| | AREA. THE DINING AREA WOULD BE CALCULATED FOR 79 |
| | OCCUPANTS. I ASSUME THE SQUARE FOOTAGE GIVEN FOR EACH |
| | OCCUPANCY CLASSIFICATION IS IN ACCORDANCE WITH FOOTNOTE |
| | A OF TABLE 403.3.1.1. FMC 403.3.1.1 |
| | |
| | 3) ADJUST THE AIR BALANCE SCHEDULE ONCE THE REQUIRED |
| | OUTDOOR AIR HAS BEEN CORRECTED. FMC 501.4 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |