Plan Review Notes
Plan Review Notes For Permit 23010224
Permit Number 23010224
Review Stop B
Sequence Number 2
Notes
Date Text
2023-02-16 13:41:41RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING ID-10 SHOWS WALL FINISH AS WB5 - WB5 IS NOT
 ON THE WALL FINISH SCHEDULE.
  
 2) DRAWING ID -10 SHOWS RESTROOM BASE BOARD AS WOOD -
 BASE BOARDS IN RESTROOMS SHOULD BE NON-ABSORBANT - FBC
 1210.2.1 FLOORS AND WALL BASES.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS NOT LESS THAN 4 INCHES.
  
  