| Date |
Text |
| 2023-01-17 11:38:58 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 23010224 831 VILLAGE BLVD # 101 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A SEPARATE PERMIT FOR INTERCEPTOR AND BACKFLOW |
| | PREVENTER AS APPLICABLE IS REQUIRED TO BE SUBMITTED |
| | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| | APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS |
| | REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN |
| | PERMIT IS ALSO REQUIRED. |
| | AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY |
| | ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS |
| | EXAMINER AT [email protected] AND RYAN BROWN, CHIEF |
| | PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH |
| | THE PERMIT NUMBER(S). |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PLEASE PROVIDE A SPECIFICATION FOR THE HOUSE SERVICE |
| | BACKFLOW PREVENTER. IF THIS IS THE PRIMARY BACKFLOW |
| | PREVENTER REQUIRED BY THE WEST PALM BEACH |
| | CROSS-CONNECTION CONTROL MANUAL, A SEPARATE PERMIT WILL |
| | BE REQUIRED. |
| | |
| | 2. PLEASE PROVIDE CALCULATIONS FOR SIZING OF GREASE |
| | INTERCEPTOR. FBC PL 1003.3.5 |
| | PLEASE NOTE, A SEPARATE PERMIT FOR THE GREASE |
| | INTERCEPTOR IS REQUIRED |
| | |
| | 3. HAND SINKS AND ICE BINS SHALL NOT DISCHARGE TO THE |
| | GREASE INTERCEPTOR. FBC PL 1003.2 |
| | |
| | 4. P4-0/DETAIL 6; NOTE 2: TEMPERED WATER SHALL BE |
| | DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| | B125.3 FOR PUBLIC LAVATORY. FBC PL 419.5, 607.1.2. |
| | PLEASE REMOVE NOTE 2 TO SHOW COMPLIANCE. |
| | |
| | 5. P4-0/DETAIL 8: PROVIDE AND SPECIFY A |
| | TEMPERATURE-ACTUATED MIXING VALVE CONFORMING TO ASSE |
| | 1017 AT EACH WATER HEATER. FBC PL 607.1.1, 613.1 |
| | |
| | 6. PER FBC PL 1002.4.1, PROVIDE TRAP SEAL PROTECTION |
| | FOR THE RESTROOM FLOOR DRAINS; PROVIDE A BOTH A TRAP |
| | SEAL PROTECTION SPECIFICATION AND A DETAIL COMPLYING |
| | WITH ONE OF THE FOLLOWING: FBC PL 1002.4.1.1, |
| | 1002.4.1.2, 1002.4.1.3 OR 1002.4.1.4. |
| | |
| | 7. DRY VENTS SHALL CONNECT ABOVE THE CENTERLINE OF THE |
| | HORIZONTAL FIXTURE DRAINS AND SHALL RISE VERTICALLY TO |
| | 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST TRAP |
| | OR TRAPPED FIXTURE BEING VENTED IN GREASY WASTE AND THE |
| | FLOOR DRAIN IN THE WOMEN'S RESTROOM . FBC PL 905.3, |
| | 905.4, 905.5 |
| | |
| | 8. PROVIDE A BACKFLOW PREVENTER CONFORMING TO ASSE 1022 |
| | IN POTABLE WATER SUPPLY TO D6 EXPRESSO COFFEE MAKER. |
| | FBC PL 608.17.1.2 |
| | |
| | 9. PROVIDE A SPECIFICATION FOR THE BACKFLOW PREVENTER |
| | ON THE POTABLE WATER SUPPLY TO THE WATER FILTERS. FBC |
| | PL 608.4 |
| | |
| | 10. PROVIDE A BACKFLOW PREVENTER ON THE POTABLE WATER |
| | SUPPLY TO THE A22 ICE MACHINE WITH BIN; PROVIDE A |
| | SPECIFICATION. FBC PL 608.3 |
| | |
| | 11. THE LONGEST LENGTH OF 1/2 INCH HOT WATER PIPE FROM |
| | THE HOT WATER SOURCE TO THE PUBLIC RESTROOM LAVATORIES |
| | SHALL NOT EXCEED 2 FEET. FBC EC C404.5.1, TABLE |
| | C404.5.1 |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |