Plan Review Notes
Plan Review Notes For Permit 23010224
Permit Number 23010224
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-17 11:38:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 23010224 831 VILLAGE BLVD # 101
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A SEPARATE PERMIT FOR INTERCEPTOR AND BACKFLOW
 PREVENTER AS APPLICABLE IS REQUIRED TO BE SUBMITTED
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. A SEPARATE PERMIT IS
 REQUIRED HOWEVER A REVIEW OF THE SYSTEM UNDER THE MAIN
 PERMIT IS ALSO REQUIRED.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, PLEASE NOTIFY
 ME AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS
 EXAMINER AT [email protected] AND RYAN BROWN, CHIEF
 PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH
 THE PERMIT NUMBER(S).
  
 PLUMBING COMMENTS: DENIED
  
 1. PLEASE PROVIDE A SPECIFICATION FOR THE HOUSE SERVICE
 BACKFLOW PREVENTER. IF THIS IS THE PRIMARY BACKFLOW
 PREVENTER REQUIRED BY THE WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL, A SEPARATE PERMIT WILL
 BE REQUIRED.
  
 2. PLEASE PROVIDE CALCULATIONS FOR SIZING OF GREASE
 INTERCEPTOR. FBC PL 1003.3.5
 PLEASE NOTE, A SEPARATE PERMIT FOR THE GREASE
 INTERCEPTOR IS REQUIRED
  
 3. HAND SINKS AND ICE BINS SHALL NOT DISCHARGE TO THE
 GREASE INTERCEPTOR. FBC PL 1003.2
  
 4. P4-0/DETAIL 6; NOTE 2: TEMPERED WATER SHALL BE
 DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3 FOR PUBLIC LAVATORY. FBC PL 419.5, 607.1.2.
 PLEASE REMOVE NOTE 2 TO SHOW COMPLIANCE.
  
 5. P4-0/DETAIL 8: PROVIDE AND SPECIFY A
 TEMPERATURE-ACTUATED MIXING VALVE CONFORMING TO ASSE
 1017 AT EACH WATER HEATER. FBC PL 607.1.1, 613.1
  
 6. PER FBC PL 1002.4.1, PROVIDE TRAP SEAL PROTECTION
 FOR THE RESTROOM FLOOR DRAINS; PROVIDE A BOTH A TRAP
 SEAL PROTECTION SPECIFICATION AND A DETAIL COMPLYING
 WITH ONE OF THE FOLLOWING: FBC PL 1002.4.1.1,
 1002.4.1.2, 1002.4.1.3 OR 1002.4.1.4.
  
 7. DRY VENTS SHALL CONNECT ABOVE THE CENTERLINE OF THE
 HORIZONTAL FIXTURE DRAINS AND SHALL RISE VERTICALLY TO
 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST TRAP
 OR TRAPPED FIXTURE BEING VENTED IN GREASY WASTE AND THE
 FLOOR DRAIN IN THE WOMEN'S RESTROOM . FBC PL 905.3,
 905.4, 905.5
  
 8. PROVIDE A BACKFLOW PREVENTER CONFORMING TO ASSE 1022
 IN POTABLE WATER SUPPLY TO D6 EXPRESSO COFFEE MAKER.
 FBC PL 608.17.1.2
  
 9. PROVIDE A SPECIFICATION FOR THE BACKFLOW PREVENTER
 ON THE POTABLE WATER SUPPLY TO THE WATER FILTERS. FBC
 PL 608.4
  
 10. PROVIDE A BACKFLOW PREVENTER ON THE POTABLE WATER
 SUPPLY TO THE A22 ICE MACHINE WITH BIN; PROVIDE A
 SPECIFICATION. FBC PL 608.3
  
 11. THE LONGEST LENGTH OF 1/2 INCH HOT WATER PIPE FROM
 THE HOT WATER SOURCE TO THE PUBLIC RESTROOM LAVATORIES
 SHALL NOT EXCEED 2 FEET. FBC EC C404.5.1, TABLE
 C404.5.1
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved