| 2023-01-17 06:29:23 | 1ST REVIEW FMC | | | PERMIT: 23010224 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET ID-5 A27, D21; LISTS THESE AS HIGH SPEED | | | OVENS, PROVIDE THE SPECS FOR THESE OVENS. PROVIDE A | | | MENU FOR THIS TENANT SHOWING WHY A HOOD IS NOT REQUIRED | | | FOR THIS TENANT SPACE. FMC 507.1 EXCEPTION NUMBER 2 | | | | | | 2) PROVIDE DUCT SMOKE DETECTORS IN THE SUPPLY SIDE OF | | | EACH RTU. FMC 606.2.2 | | | | | | 3) PROVIDE OUTDOOR AIR CALCULATIONS BASED ON THE | | | OCCUPANT DENSITY FOUND IN TABLE 403.3.1.1. FMC | | | 403.3.1.1 | | | | | | 4) PROVIDE THE MINIMUM KITCHEN EXHAUST REQUIRED IN | | | TABLE 403.3.1.1. FMC 507.1 EXCEPTION NUMBER 2 | | | | | | 5) WITH THE KITCHEN EXHAUST, SHOW THAT THE MECHANICAL | | | DESIGN FOR THE ROOM OR SPACE SHALL BE MAINTAINED WITH A | | | NEUTRAL OR NEGATIVE PRESSURE. FMC 501.4 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|