Plan Review Notes
Plan Review Notes For Permit 23010224
Permit Number 23010224
Review Stop E
Sequence Number 1
Notes
Date Text
2023-01-18 15:56:35ELECTRIC REVIEW FAILED
 1) PLEASE INDICATE ALL RECEPTACLES AS OUTLINED IN NEC
 210.8(B)(2) KITCHENS (BELOW) AS GFCI PROTECTED.
  
 THE NEC DEFINITION OF KITCHEN IS ???AN AREA WITH A SINK
 AND PERMANENT FACILITIES FOR FOOD PREPARATION AND
 COOKING.???
  
 NEC 210.8(B)(2). ALL KITCHEN SINGLE-PHASE RECEPTACLES
 RATED 150 VOLTS TO GROUND OR LESS, 50 AMPERES OR LESS
 AND THREE-PHASE RECEPTACLES RATED 150 VOLTS TO GROUND
 OR LESS, 100 AMPERES OR LESS INSTALLED IN THE FOLLOWING
 LOCATIONS SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL
  
 2) PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED
 SEPARATE PERMITS FOR, ALL LOW VOLTAGE SYSTEMS TO
 INCLUDE BUT NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS,
 CCTV, PHONE AND DATA, SIGNAGE, WIRELESS SYSTEMS,
 ELEVATORS, KITCHEN HOOD SYSTEMS, WALK IN COOLERS ETC. A
 NOTE WILL SUFFICE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  