| 2023-01-18 15:56:35 | ELECTRIC REVIEW FAILED |
| | 1) PLEASE INDICATE ALL RECEPTACLES AS OUTLINED IN NEC |
| | 210.8(B)(2) KITCHENS (BELOW) AS GFCI PROTECTED. |
| | |
| | THE NEC DEFINITION OF KITCHEN IS ???AN AREA WITH A SINK |
| | AND PERMANENT FACILITIES FOR FOOD PREPARATION AND |
| | COOKING.??? |
| | |
| | NEC 210.8(B)(2). ALL KITCHEN SINGLE-PHASE RECEPTACLES |
| | RATED 150 VOLTS TO GROUND OR LESS, 50 AMPERES OR LESS |
| | AND THREE-PHASE RECEPTACLES RATED 150 VOLTS TO GROUND |
| | OR LESS, 100 AMPERES OR LESS INSTALLED IN THE FOLLOWING |
| | LOCATIONS SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL |
| | |
| | 2) PLEASE PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| | SEPARATE PERMITS FOR, ALL LOW VOLTAGE SYSTEMS TO |
| | INCLUDE BUT NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS, |
| | CCTV, PHONE AND DATA, SIGNAGE, WIRELESS SYSTEMS, |
| | ELEVATORS, KITCHEN HOOD SYSTEMS, WALK IN COOLERS ETC. A |
| | NOTE WILL SUFFICE. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |