| 2023-02-15 09:02:09 | |
| | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 23010196 |
| | ADD: 700 S. ROSEMARY AVE. |
| | CONT: PROMETHEAN BUILDERS |
| | TEL: 561-818-8054 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 15TH/2023 |
| | ACTION: DENIED |
| | |
| | 1) CITY PLACE MANAGEMENT STAMP OF APPROVAL. THE CITY |
| | PLACE RETAIL MANAGEMENT APPROVAL STAMP IS REQUIRED ON |
| | THE PLANS. FOR AN ALTERNATE, YOU MAY PROVIDE A LETTER |
| | FROM CITY PLACE RETAIL MANAGEMENT WHICH APPROVES THE |
| | SPECIFIC PLANS SUBMITTED UNDER THIS PERMIT. |
| | |
| | 2) NEITHER THE ARCHITECTURAL NOR STRUCTURAL SHEETS |
| | PROVIDE THE PROPOSED MINIMUM LIVE LOAD DESIGN OF THE |
| | STAIRWAY. 2020 FBC-BUILDING CODE TABLE 1607.1(30). |
| | |
| | 3) SHEET S-1.0 THERE IS A STATEMENT ON THE PLAN, G. C. |
| | SHALL VERIFY RECESS @ BEAM EDGE, CHIP DOWN EXISTING |
| | EDGE AS REQUIRED. THERE IS NO DIMENSION AS HOW FAR THEY |
| | CAN GO, OR IF NOTIFICATION TO THE STRUCTURAL ENGINEER |
| | IS REQUIRED. THIS IS CONSIDERED A THRESHOLD BUILDING. |
| | CITY PLACE MANAGEMENT STAMP OF APPROVAL. THE CITY PLACE |
| | RETAIL MANAGEMENT APPROVAL STAMP IS REQUIRED ON THE |
| | PLANS. FOR AN ALTERNATE, YOU MAY PROVIDE A LETTER FROM |
| | CITY PLACE RETAIL MANAGEMENT WHICH APPROVES THE |
| | SPECIFIC PLANS SUBMITTED UNDER THIS PERMIT. |
| | |
| | 4) THE PARKING GARAGE IS A 5-STORY STRUCTURE MAKING |
| | THIS A THRESHOLD BUILDING AND HAVING TO MEET THE |
| | REQUIREMENTS OF / FL S. S. 553.71(7) FOR THRESHOLD |
| | BUILDING. FL S. S. 553.71(7) ???THRESHOLD BUILDING" |
| | MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES |
| | OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE |
| | WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 4A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 4B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | THRESHOLD FORMS E-MAILED TO: |
| | [email protected] |
| | |
| | 4C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 4D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 4E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT |
| | REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| 2023-02-15 08:12:32 | STAIR REPLACEMENT |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE SHOW STAIR RISER HEIGHT - FBC 1011.5.2 RISER |
| | HEIGHT AND TREAD DEPTH. |
| | STAIR RISER HEIGHTS SHALL BE 7 INCHES (178 MM) MAXIMUM |
| | AND 4 INCHES (102 MM) MINIMUM. |
| | |
| | 2) PLYWOOD USED SHOULD BE SHOWN AS FIRE RETARDANT - FBC |
| | 603.1 |