Plan Review Notes
Plan Review Notes For Permit 23010193
Permit Number 23010193
Review Stop E
Sequence Number 1
Notes
Date Text
2023-01-30 11:46:26ELECTRIC REVIEW FAILED
  
 1) PLEASE PROVIDE AN ELECTRIC FLOOR PLAN DETAILING ALL
 NEW AND EXISTING ELECTRIC WORK. CLEARLY DISTINGUISH NEW
 WORK VERSUS WORK TO REMAIN. PLEASE INCLUDE ALL NEW
 APPLIANCES TO BE INSTALLED. FBC 107.2, CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL
  
 2) PLEASE PROVIDE KITCHEN COUNTER AND APPLIANCE LAYOUT
 AND DETAIL ALL ELECTRICAL RECEPTACLES AS REQUIRED PER
 NEC 210.52. A RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH WALL COUNTERTOP AND WORK SURFACE THAT IS 300 MM
 (12 IN.) OR WIDER. RECEPTACLE OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 600 MM (24 IN.) MEASURED HORIZONTALLY FROM A
 RECEPTACLE OUTLET IN THAT SPACE
  
 3) PLEASE PROVIDE AN ELECTRIC PANEL SCHEDULE DETAILING
 ALL CIRCUITS REQUIRED, CONDUCTOR SIZES AND OVERCURRENT
 PROTECTION FOR EACH CIRCUIT. PLEASE INDICATE WHETHER
 CIRCUIT IS NEW OR EXISTING. FBC 107.2 AND NEC 215.5
  
 4) PLEASE PROVIDE AN ACCURATE ELECTRIC RISER DETAILING
 ELECTRIC PANEL, CONDUIT, CONDUCTOR AND OVERCURRENT
 PROTECTION SIZES. PLEASE INDICATE EQUIPMENT AS NEW OR
 EXISTING. NEC 215.5
  
 5) PROVIDE AN ELECTRIC LOAD CALCULATION DETAILING ALL
 ELECTRIC LOADS, AND APPLIANCES SUCH AS WATER HEATERS,
 RANGES, AIR CONDITIONING EQUIPMENT, ETC. NEC 220.40,
 THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT BE
 LESS THAN THE SUM OF THE LOADS ON THE BRANCH CIRCUITS
 SUPPLIED
  
 6) PLEASE DETAIL RECEPTACLES THAT APPEAR TO BE MISSING
 IN ACCORDANCE WITH NEC 210.52, RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 1.8
 M (6 FT) FROM A RECEPTACLE OUTLET AND ANY SPACE 600 MM
 (2 FT) OR MORE IN WIDTH
  
 7) PLEASE INDICATE BY NOTE ALL NEW WIRING IS TO COMPLY
 WITH NEC 210.8 FOR GFCI PROTECTION, NEC 210.12 ARC
 FAULT PROTECTION, AND NEC 406.12 FOR TAMPER RESISTANT
 RECEPTACLE REQUIREMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  