| Plan Review Notes For Permit 23010192 |
| Permit Number |
23010192 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-27 14:49:03 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-23010192 | | | 1/27/2023 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P-100.02 & P-200.01: THE PLANS SHOW HAND | | | SINKS #6, #207A DRAINS, AND THE ICE BIN 207E DRAIN | | | DISCHARGING INTO THE GREASE WASTE LINE WHICH IS | | | PROHIBITED PER SEC. 1003.3.1 FBC P. GREASE INTERCEPTORS | | | SHALL RECEIVE WASTE ONLY FROM FIXTURES THAT ALLOW FATS, | | | OILS, OR GREASE TO BE DISCHARGED. | | | | | | 2) P-200.01 DETAIL 2: THE DETAIL DOES NOT SHOW HOT | | | WATER CONNECTIONS TO THE SINKS (207A & 207B) & THE | | | PITCHER RINSER (207F). HOT WATER IS REQUIRED PER SEC. | | | 607.1 FBC P. | | | | | | 3) P-200.01: PLEASE DETAIL THE MEANS OR METHOD USED TO | | | LIMIT THE HOT WATER TEMPERATURE DELIVERY FROM THE | | | SINKS- SEC. 607.1.1 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|