| 2023-01-17 15:31:58 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 23010183 |
| | 1/17/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) POOL PLANS HAVE NOT BEEN SUBMITTED FOR REVIEW AS |
| | REQUIRED BY SECS. 107.2.1 & 107.3.5.4 WPB. PLEASE |
| | SUBMIT COMPLETE PLANS INCLUDING A POOL PLUMBING SITE |
| | PLAN THAT SHOWS THE PIPING RUNS FROM THE POOL TO THE |
| | RECIRCULATION EQUIPMENT. |
| | A) PROVIDE A PIPING DIAGRAM OR SCHEMATIC DRAWING |
| | SHOWING THE PRESSURE AND SUCTION PIPE SIZES AND FPM |
| | FLOWS- SEC. R4501.6.3 FBC RES. |
| | B) PROVIDE POOL AND SPA SPECIFICATIONS INCLUDING THE |
| | POOL SIZE, DEPTH, AREA, VOLUME IN GALLONS, DESIGN FLOW |
| | RATE, SYSTEM FLOW RATE, AND TURNOVER TIME- SEC. |
| | R4501.6.1 FBC RES. |
| | C) PROVIDE A RECIRCULATION EQUIPMENT SCHEDULE THAT |
| | INCLUDES THE MAKES AND MODELS OF THE PUMP, FILTER, |
| | CHLORINATOR, HEATER (IF APPLICABLE), AND UNBLOCKABLE |
| | DRAIN ASSEMBLY INCLUDING FLOW RATE- SECS. R4501.6.2, |
| | R4501.6.6, R4501.7.2, R4501.20 & R4501.21.3 FBC RES. |
| | D) PROVIDE TDH CALCULATIONS, AND THE PUMP CURVE ON THE |
| | PLAN MARKED UP TO SHOW THE TDH AND FLOW RATE OF THE |
| | SYSTEM- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & |
| | R4501.7.2 & R4501.7.3 FBC RES. |
| | |
| | 2) PROVIDE ON THE PLAN A LIST OF CONFORMANCE STANDARDS |
| | IN COMPLIANCE WITH SEC. R4501.6.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |