Plan Review Notes
Plan Review Notes For Permit 23010183
Permit Number 23010183
Review Stop P
Sequence Number 1
Notes
Date Text
2023-01-17 15:31:581ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 23010183
 1/17/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) POOL PLANS HAVE NOT BEEN SUBMITTED FOR REVIEW AS
 REQUIRED BY SECS. 107.2.1 & 107.3.5.4 WPB. PLEASE
 SUBMIT COMPLETE PLANS INCLUDING A POOL PLUMBING SITE
 PLAN THAT SHOWS THE PIPING RUNS FROM THE POOL TO THE
 RECIRCULATION EQUIPMENT.
 A) PROVIDE A PIPING DIAGRAM OR SCHEMATIC DRAWING
 SHOWING THE PRESSURE AND SUCTION PIPE SIZES AND FPM
 FLOWS- SEC. R4501.6.3 FBC RES.
 B) PROVIDE POOL AND SPA SPECIFICATIONS INCLUDING THE
 POOL SIZE, DEPTH, AREA, VOLUME IN GALLONS, DESIGN FLOW
 RATE, SYSTEM FLOW RATE, AND TURNOVER TIME- SEC.
 R4501.6.1 FBC RES.
 C) PROVIDE A RECIRCULATION EQUIPMENT SCHEDULE THAT
 INCLUDES THE MAKES AND MODELS OF THE PUMP, FILTER,
 CHLORINATOR, HEATER (IF APPLICABLE), AND UNBLOCKABLE
 DRAIN ASSEMBLY INCLUDING FLOW RATE- SECS. R4501.6.2,
 R4501.6.6, R4501.7.2, R4501.20 & R4501.21.3 FBC RES.
 D) PROVIDE TDH CALCULATIONS, AND THE PUMP CURVE ON THE
 PLAN MARKED UP TO SHOW THE TDH AND FLOW RATE OF THE
 SYSTEM- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 &
 R4501.7.2 & R4501.7.3 FBC RES.
  
 2) PROVIDE ON THE PLAN A LIST OF CONFORMANCE STANDARDS
 IN COMPLIANCE WITH SEC. R4501.6.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  