| Plan Review Notes For Permit 23010156 |
| Permit Number |
23010156 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-02-01 14:17:02 | FLOOR REPAIR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING S4 IS MISSING - THERE ARE CUT SECTIONS THAT | | | REFER TO S4. | | | | | | 2) PLEASE SHOW JOIST ANCHORAGE FBC 107 | | | | | | 3) SIGNED AND SEALED DRAWINGS NEED TO BE DIGITALLY | | | SIGNED BY THE DESIGNER - SIGNED AND SEALED DRAWINGS IN | | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE). | | | I CHECK THE ELECTRONIC SIGNATURE BY OPENING THEM IN | | | ???ADOBE READER???. THE ???ADOBE READER??? STATES | | | WHETHER THEY ARE AN ORIGINAL ELECTRONICALLY SIGNED | | | DOCUMENT. WHEN ELECTRONICALLY SIGNED DRAWINGS ARE | | | PRINTED OUT, THEY LOSE THEIR ELECTRONIC SIGNATURE. | | | ELECTRONICALLY SIGNED DRAWINGS NEED TO BE MOVED AROUND | | | IN THE COMPUTER FROM PLACE TO PLACE. FROM THE | | | ARCHITECT???S OR ENGINEER???S COMPUTER TO YOUR COMPUTER | | | TO THE CITY???S ELECTRONIC PLAN REVIEW (PROJECTDOX). | | | MAYBE YOURS WERE PRINTED OUT AT SOME TIME? |
|