Plan Review Notes
Plan Review Notes For Permit 23010109
Permit Number 23010109
Review Stop M
Sequence Number 1
Notes
Date Text
2023-02-07 10:44:441ST REVIEW FMC
 PERMIT: 23010109
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IS THIS A CHANGE OUT OF AN EXISTING DIESEL
 GENERATOR? IF NOT PLEASE PROVIDE THE GENERATOR SPECS.
  
 2) HOW IS THE FUEL TANK FOR THIS GENERATOR TO BE
 FILLED? PROVIDE A MECHANICAL DRAWING SHOWING THE PIPING
 AND FILL STATION FOR THE DIESEL GENERATOR. FBC 107.3.5
  
 3) PROVIDE A SITE MAP THAT SHOWS THE DIESEL EXHAUST
 FROM THE GENERATOR IS 10 FEET FROM THE PROPERTY LINES.
 FMC 501.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  